01.2004Installation

Water cooling

The units with water cooling (MLFB Annex: -1AC0) are suitable for

 

installing in an enclosed cabinet (IP54). The mains filter connection

 

module is identical for water and air cooling. The components not

 

mounted on the heat sink, such as the electronics and the DC link

 

capacitors are cooled by heat transfer at the heat sink fins. To enable

 

this heat transfer to take place, air circulation inside the unit is

 

necessary.

 

Therefore, when installing the chassis unit in a cabinet, you must make

 

sure that the air being discharged from the fan can flow into the inside

 

of the chassis. The partitions to be provided in units with air cooling

 

are a disturbing factor in this case! They should not be mounted.

 

For an application in the types of protection > IP40, a distance of at

 

least 90 mm must be observed between the top of the units and the top

 

of the cabinet.

 

The units do not require external cooling air.

 

Additional losses cannot be dissipated!

 

1-inch internal threads are envisaged for the water connection. The

 

connecting nipples should be made of stainless steel or thick-walled

 

aluminium. Ideally, the connection should have flat seals. If the

 

connecting pieces enclosed with the units are used, these should be

 

sealed with Loctite 542 or with teflon tape.

 

Cooling water infeed (blue) and return (red) must be connected

 

according to the color scheme! The color markings can be found next to

 

the 1-inch water connection below the heat sink.

Built-in components

If components are built into a cabinet roof section (DC bus, DC 24 V

in the roof section

supply), these should be placed in the center if possible so that the air

 

leaving the fans can reach the openings in the roof cover unobstructed.

Siemens AG 6SE7087-6CX86-2BA1

5-7

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 25
Image 25