Installation

01.2004

 

 

Water cooling

Inverters with water cooling (item number suffix: -1AA0) are suitable for

 

mounting in enclosed cabinets (IP54). The components not mounted on

 

the heat sink, such as the electronics and the DC link capacitors, are

 

cooled by heat transfer at the heat sink fins. To enable this heat

 

transfer to take place, air circulation inside the unit is necessary.

 

Therefore, when installing the chassis unit in a cabinet, you must make

 

sure that the air being discharged from the fan can flow into the inside

 

of the chassis. The partitions to be provided in units with air cooling

 

are a disturbing factor in this case! They should not be mounted.

 

For an application in the types of protection > IP40, a distance of at

 

least 90 mm must be observed between the top of the units and the top

 

of the cabinet.

 

The units do not require external cooling air.

 

Additional losses cannot be dissipated!

 

1-inch internal threads are envisaged for the water connection. The

 

connecting nipples should be made of stainless steel or thick-walled

 

aluminum. Ideally, the connection should have flat seals. If the

 

connecting pieces enclosed with the units are used, these should be

 

sealed with Loctite 542 or with teflon tape.

 

Cooling water infeed (blue) and return (red) must be connected

 

according to the color scheme! The color markings can be found next to

 

the 1-inch water connection below the heat sink.

Built-in components

If components are built into a cabinet roof section (DC bus, DC 24 V

in the roof section

supply), these should be placed in the center if possible so that the air

 

leaving the fans can reach the openings in the roof cover unobstructed.

Implementation of

In order to ensure fault-free operation of the equipment (in terms of

24 V DC auxiliary

electromagnetic compatibility), it is advisable to provide each chassis

supply

unit with its own 24 V DC auxiliary supply with isolating transformer.

5-12

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 30
Image 30
Siemens 400 V / 210...590 A operating instructions Implementation, DC auxiliary, Supply