01.2004

Control and Status Words

 

 

Bit #

 

Value

1 = High

Select

 

 

 

0 = Low

destin.

Bit 0

1

Ready for ON

P600.x

Value

Destination

 

0

Not ready for ON

 

Bit 1

1

Ready to RUN

P601.x

 

0

Not ready to RUN

 

Bit 2

1

Run

P602.x

 

0

Inv. pulses inhibited

 

Bit 3

1

Fault

P603.x

 

0

No fault

 

Bit 4

1

No OFF2

P604.x

 

0

OFF2

 

Bit 5

 

Reserved

 

Bit 6

1

Starting lockout

P606.x

 

0

No starting lockout

 

Bit 7

1

Alarm

P607.x

 

0

No alarm

 

Bit 8

1

No setp./act.v. deviation

P608.x

 

0

Setp./act. val. deviation

 

Bit 9

1

PZD control requested

always 1

 

0

(not permitted)

 

Bit 10

 

Reserved

 

Bit 11

1

"Undervoltage" fault

P611.x

 

0

No "Undervolts." fault

 

Bit 12

1

MC energized

P612.x

 

0

MC not energized

 

Bit 13

 

Reserved

 

Bit 14 1)

1

Generator operation

P614.x

 

0

Motor operation

 

Bit 15

 

Reserved

 

x = 1 0000 1001 1002 1003 1004

0000

4101

4102

4103

4104

4105

4106

4107

4108

4109

4110 x = 2 4111 4112 4201 4202 4203 4204 4205 4206 4207 4208 4209 4210 4211 4212

x = 3 0000 5001 5002

No destination

Assigned (precharging)

Assigned (main contactor)

BA3, -X102:29/33

BA4, -X102:32/33

No destination

SCI 1/2, slave 1, BA1

SCI 1/2, slave 1, BA2

SCI 1/2, slave 1, BA3

SCI 1/2, slave 1, BA4

SCI 1/2, slave 1, BA5

SCI 1/2, slave 1, BA6

SCI 1/2, slave 1, BA7

SCI 1/2, slave 1, BA8

SCI 2 only, slave 1, BA9

SCI 2 only, slave 1, BA10

SCI 2 only, slave 1, BA11

SCI 2 only, slave 1, BA12

SCI 1/2, slave 2, BA1

SCI 1/2, slave 2, BA2

SCI 1/2, slave 2, BA3

SCI 1/2, slave 2, BA4

SCI 1/2, slave 2, BA5

SCI 1/2, slave 2, BA6

SCI 1/2, slave 2, BA7

SCI 1/2, slave 2, BA8

SCI 2 only, slave 2, BA9

SCI 2 only, slave 2, BA10

SCI 2 only, slave 2, BA11

SCI 2 only, slave 2, BA12

No destination

TSY, BA1

TSY, BA2

1) This bit corresponds to bit "CW/CCW rotation" on the MASTERDRIVES CUVC

Siemens AG 6SE7087-6CX86-2BA1

13-15

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 125