Basic Function Check

 

 

Checking actual value acquisition and precharging

Issue the ON command via PMU (by default, ON command P554 already set on PMU)

Reaction: Precharging begins with picking up of the contactor -K4, and the DC link voltage (see display parameter r006) rises within approximately 1 second to the final value, approximately 1.35 times the mains voltage. The main contactor -K1 is connected once the final value has been reached.

Contacts: cf. section entitled "Control connections"

Main contactor ON command from CUSA X100 terminal 6 (M24)-7 signal from normally-open CUSA binary output 2

This command is forwarded to the mains angle acquisition circuit

VSB: connector X3: terminal 5 signal X3: terminal 1 M24

Output to potential-free contact VSB: X2 terminal 1: 230 V AC

X2 terminal 3: to coil of main contactor -K1

Reaction: Once the main contactor -K1 has picked up, the precharging contactor -K4 opens after approx. 500 ms.

Status: 0011 "Ready to Run"

The AFE inverter is now in the "Ready to Run " state and the following actual values must be correctly displayed: r032: Mains frequency tolerance ± 2 %

r030: Mains voltage, currently applied RMS value tolerance ± 2 %

If the fault F004 occurs, check the mains direction of rotation, check the main contactor's contacts and check the mains voltage.

Siemens AG 6SE7087-6CX86-2BA1

8-3

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 55
Image 55
Siemens 400 V / 210...590 A operating instructions Checking actual value acquisition and precharging