Siemens 400 V / 210...590 A operating instructions Initial Start-Up

Models: 400 V / 210...590 A

1 166
Download 166 pages 35.09 Kb
Page 14
Image 14

01.2004

Initial Start-Up

 

 

3 Initial Start-Up

Unpack and check the

units

Fit the main

components of the unit and install options that have not already been fitted

Wire the main

components of the unit

and connect the PE conductor and the power cables

Form the DC link

capacitors, if necessary

Connect the 230 V AC auxiliary voltage or the 24 V DC and the mains voltage

If necessary, carry out

parameter reset to

factory setting

After removing the packaging, check that the unit is intact and undamaged. Only intact units may be started up. Please also check that all the necessary option boards are present and correct.

Retrofit any optional boards which have not yet been installed, if necessary. Then install the units taking into account the requirements at the point of installation and the EMC instructions.

Beginning with the PE conductor, connect the power cables and the power wiring of the AFE chokes. It is advisable to not yet connect the DC link module.

Use only the included cable harnesses for further internal wiring of the main conponents. In this step, do not yet connect the control and communication cables. Exception: OP1S if the unit is to be parametrized via OP1S.

If the unit's DC link was de-energized for more than a year, the DC link capacitors must be formed again. .

Note: under no circumstances must the main contactor -K1 and the precharging contactor -K4 be connected in this phase; therefore, check the unit before connecting the mains voltage.

After checking the cabling for correct connection and secure attachment, connect the mains voltage or the auxiliary power supply. After the electronics power supply has been started, the unit initializes itself. The action can take several seconds. The drive status is subsequently shown on the PMU.

If the PMU does not show status °009 after completion of the unit initialization, or if the unit has already been parameterized before, you should carry out a parameter reset to factory setting.

See section "Transport, Storage, Unpacking"

See section "Installation" and "Installation in Conformance with EMC Regulations"

See chapters

"Connecting and

wiring" and

"Installation in conformance with EMC Regulations"

See section

"Forming"

See chapter

entitled "Basic function check"

See section

"Parameterization"

Siemens AG 6SE7087-6CX86-2BA1

3-1

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 14
Image 14
Siemens 400 V / 210...590 A operating instructions Initial Start-Up