Parameterization

 

 

11.2.5Hardware configuration (P052 = 4)

Function

The purpose of this function is to define option boards (SCB, TSY, CB,

 

TB) installed in the electronics box of the converter.

Condition

The "Hardware configuration" function can be selected in the FAULT

 

(007), STARTING LOCKOUT (008) or READY FOR ON (009) states.

 

The LBA bus link (Local Bus Adapter) is required additionally to install

 

option boards in the electronics box. See Section "Interfaces".

Result

All parameters which can be written in the "Hardware configuration"

 

state ("H", see right-hand column in "Parameter List") can be altered.

P052 = 4

Select "Hardware configuration"

P051 = 3

P090 =

P091 =

NOTE

Access level "Expert Mode"

(to be able to alter the following parameters)

Board in slot 2 ( RIGHT in electronics box)

Board in slot 3 ( CENTRE in electronics box!)

Parameter values for P090/P091:

0:No option board

1:CB Communication Board

2:TB Technology Board (P090 only)

3:SCB Serial Communication Board

4:TSY Digital Tacho and Synchronization Board

Slot in electronics box

Boards

Left

Slot 1

(CU)

CUSA

 

 

 

 

Centre

Slot 3

(options)

CB / SCB1 / SCB2 / (TSY, not with TB)

Right

Slot 2

(options)

CB / SCB1 / SCB2 / TSY / TB

 

 

 

 

Only one of each option board type may be inserted in the electronics box at one time.

Technology boards (e.g. T300) must always be inserted in slot 2. The TSY board may not be inserted at the same time as a TB.

If only one option board is in use, it must always be inserted in slot 2.

Other parameters depending on option boards

(see relevant Operating Instructions or Parameter List).

Make selection between:

Siemens AG 6SE7087-6CX86-2BA1

11-9

SIMOVERT MASTERDRIVES AFE Operating Instructions