01.2004

 

 

 

 

 

Parameter List

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PNU

 

Parameter Name in OP1

 

Range

# of Indices

read:

_/_

 

 

 

 

 

 

 

[Unit]

Factory

write:

_/_

 

 

*:conf-P

 

Description

 

 

Value Texts

Settings

 

 

 

 

 

 

r303

 

Vd(act)

 

 

 

3 /

BR

 

 

 

 

12FHex

 

Actual unsmoothed DC-link voltage value

[V]

 

 

 

 

 

 

 

 

Analog output: 100 % with code number (PWE) = 4 x P071

 

 

 

 

 

 

 

 

 

 

Type=I2;

PKW: 1HEX=1 V

PZD Gr.: 7

 

 

 

 

 

 

 

 

P308

 

Sampling Time

 

0.8 to 4.0

3 /

ABR

 

 

 

 

134Hex

 

Basic sampling time T0.

 

[ms]

1.5

3 /

A

 

 

 

 

 

Setting instructions:

 

 

 

 

 

 

 

 

 

 

 

When the sampling time is reduced, the available

 

 

 

 

 

 

 

 

 

 

computing time should be checked via parameter r725 in

 

 

 

 

 

 

 

 

 

 

the "Run" state. At least 5 % of the available computing

 

 

 

 

 

 

 

 

 

 

time should always be left in reserve to avoid any delayed

 

 

 

 

 

 

 

 

 

 

(slow) execution of operator inputs.

 

 

 

 

 

 

 

 

 

 

If fault F042 "Computing time" occurs, the sampling time

 

 

 

 

 

 

 

 

 

 

setting must be increased again.

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=0.1 ms

PZD Gr.:

 

 

 

 

 

 

 

P325

 

MC switch-on del

 

0.0 to 30.0

3 /

BR

 

 

 

145Hex

 

Delay time for closing (energizing) the main contactor.

[s]

0.0

3 /

B

 

 

 

 

By delaying energization of the main contactor, it is possible to

 

 

 

 

 

 

 

 

 

 

charge the DC link up to the line voltage peak value via the

 

 

 

 

 

 

 

 

 

 

precharging resistors. This measure will be necessary if the

 

 

 

 

 

 

 

 

 

 

external DC-link capacitance connected to the AFE is

 

 

 

 

 

 

 

 

 

 

significantly higher than that of the AFE.

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=0.1 s

PZD Gr.:

 

 

 

 

 

 

 

 

P326

 

Max.pre-chrg. t.

 

0.1 to 30.0

2

3 /

BR

 

 

 

 

146Hex

 

Maximum precharging time

 

[s]

i001=3.0

3 /

B

 

 

 

 

 

If the DC link is not successfully precharged within this period,

 

i002=3.0

 

 

 

 

 

 

 

 

fault message Precharging (F002) or, if the line voltage is too

 

 

 

 

 

 

 

 

 

 

low, fault message Line Voltage (F004) is activated.

 

 

 

 

 

 

 

 

 

 

RDS(2) parameter

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=0.1 s

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P329

 

MCInvEnableDel

 

0.08 to 5.00

4 /

BR

 

 

 

 

149Hex

 

Delay between activation of the main contactor and enabling

[s]

0.40

4 /

BR

 

 

 

 

 

of the inverter.

 

 

 

 

 

 

 

 

 

 

 

By increasing this time, it is possible to ensure that the DC link

 

 

 

 

 

 

 

 

 

 

is charged up completely to the peak value of the mains

 

 

 

 

 

 

 

 

 

 

voltage. This is necessary if the external DC link capacity

 

 

 

 

 

 

 

 

 

 

connected to the AFE is considerably greater than that of the

 

 

 

 

 

 

 

 

 

 

AFE. The set time should always be at least 100 ms greater

 

 

 

 

 

 

 

 

 

 

than the time that the main contactor needs to close the

 

 

 

 

 

 

 

 

 

 

contacts.

 

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=0.o1 s

PZD-Gr.:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Siemens AG 6SE7087-6CX86-2BA1

12-13

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 83
Image 83