01.2004

 

 

 

 

 

 

Faults and Alarms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fault messages

 

 

No.

 

 

Description of fault

 

 

 

Remedial measures

 

 

F025

 

UCE Ph. L1

 

 

Check

 

 

 

 

A UCE shutdown has occurred in phase L1

 

 

phase L1 for short circuit or earth fault

 

 

 

 

 

 

 

(-X2:U2 - including motor).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the contacts on the CU.

 

 

F026

 

UCE Ph. L2

 

 

Check

 

 

 

 

A UCE shutdown has occurred in phase L2

 

 

phase L2 for short circuit or earth fault

 

 

 

 

 

 

 

(-X2:V2 - including motor).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the contacts on the CU.

 

 

F027

 

UCE Ph. L3

 

 

Check

 

 

 

 

A UCE shutdown has occurred in phase L3

 

 

phase L3 for short circuit or earth fault

 

 

 

 

 

 

 

(-X2:W2 - including motor).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the contacts on the CU.

 

 

F029

 

Meas. val. sensing

 

 

Defect in the measured value sensing circuit

 

 

 

 

A fault has occurred in the measured value sensing

 

 

Defect in the power section (valve is not blocking)

 

 

 

 

circuit.

 

 

 

 

 

 

 

 

 

(r949 = 1) Offset cannot be adjusted in phase L1.

 

 

 

 

 

 

 

 

 

(r949 = 2) Offset cannot be adjusted in phase L2.

 

 

 

 

 

 

 

 

 

(r949 = 3) Offset cannot be adjusted in phases L1 and

 

 

 

 

 

 

 

 

 

 

L3.

 

 

 

 

 

 

 

F030

 

DC-link short circuit

 

 

Check the DC link

 

 

 

 

A short circuit has been detected during DC-link

 

 

 

 

 

 

 

 

 

precharging.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F035

 

Ext. fault 1

 

 

Check

 

 

 

 

Parameterizable external fault input 1 has been activated

 

 

whether an external fault has occurred

 

 

 

 

 

 

whether the lead to the appropriate digital input is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

interrupted

 

 

 

 

 

 

 

 

P575 Src No Ext Fault1

 

 

 

 

 

 

 

 

See section "Digital inputs" in Operator's Guide

 

 

F036

 

Ext. fault 2

 

 

Check

 

 

 

 

Parameterizable external fault input 2 has been activated

 

 

whether an external fault has occurred

 

 

 

 

 

 

whether the lead to the appropriate digital input is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

interrupted

 

 

 

 

 

 

 

 

P586 Src No Ext Fault2

 

 

 

 

 

 

 

 

See section "Digital inputs" in Operator's Guide

 

 

 

 

 

 

 

 

 

 

F039

 

DC link ground fault

 

 

Check:

 

 

 

 

An earth fault has been detected during DC-link

 

 

Maximum connected inverter power greater than

 

 

 

 

 

 

4 x AFE inverter power?

 

 

 

 

precharging

 

 

 

 

 

 

 

 

If No: Check the DC link

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If Yes: Contact your local SIEMENS AG branch

 

 

 

 

 

 

 

 

 

 

F040

 

AS internal

 

 

Replace the CUSA (-A10) board

 

 

 

 

Incorrect operating status

 

 

 

 

 

 

 

F041

 

EEprom fault

 

 

Replace the CUSA (-A10) board

 

 

 

 

A fault occurred as values were been saved to the

 

 

 

 

 

 

 

 

 

EEPROM

 

 

 

 

 

 

 

F042

Comp. time

 

 

Reduce the computation time load, increase P308

 

 

 

 

Computation time problems

 

 

Sampling time,

 

 

 

 

 

 

 

 

check r725 Available computation time.

 

 

F045

 

Opt.brd.HW

 

 

Replace the CUSA board

 

 

 

 

A hardware fault occurred as an option board was being

 

 

Check the connection between the subrack and option

 

 

 

 

accessed

 

 

 

 

 

 

 

 

boards

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Siemens AG 6SE7087-6CX86-2BA1

14-3

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 134
Image 134
Siemens 400 V / 210...590 A operating instructions 14-3