12.1General visualization parameters

 

PNU

 

 

Parameter Name in OP1

 

 

Range

# of Indices

read:

_/_

 

 

 

 

 

 

 

 

 

 

[Unit]

Factory

write:

_/_

 

*:conf-P

 

 

Description

 

 

 

Value Texts

Settings

 

 

 

 

r000

 

 

Operation Display

 

 

 

 

1 /UHABR

 

 

 

 

Displays the operating status, fault and alarm messages

 

 

 

 

 

 

 

 

 

 

See Section “Operator control" for a description

 

 

 

 

 

 

 

r001

 

 

Operating status

 

 

 

 

2 /UHABR

 

 

 

 

Visualization parameter indicating the current operating state

 

 

 

 

 

 

 

1Hex

 

 

of the AFE

 

 

 

 

 

 

 

 

 

 

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

0

=

AFE MLFB input

 

 

MLFB Input

 

 

 

 

 

 

 

1

=

AFE initialization

 

 

Init. MLFB

 

 

 

 

 

 

 

2

=

Hardware initialization

 

 

H/W Init

 

 

 

 

 

 

 

3

=

Closed-loop control initialization

 

 

System Init

 

 

 

 

 

 

 

4

=

Hardware settings (H)

 

 

H/W Setting

 

 

 

 

 

 

 

5

=

Closed-loop control settings (A)

 

 

System Set.

 

 

 

 

 

 

 

7

=

Fault

 

 

 

Fault

 

 

 

 

 

 

 

8

=

Starting lockout

 

 

ON locked

 

 

 

 

 

 

 

9

=

Ready for ON

 

 

Rdy ON

 

 

 

 

 

 

 

10

=

DC-link precharging

 

 

Precharging

 

 

 

 

 

 

 

11

=

Ready to run

 

 

Rdy Run

 

 

 

 

 

 

 

14

=

Run

 

 

 

Operation

 

 

 

 

 

 

 

18

=

Forming

 

 

 

Capacitor

 

 

 

 

 

 

 

21

=

Downloading parameter settings ....

 

 

forming

 

 

 

 

 

 

 

 

Analog output: 100 % with code number (PWE) = 16384

 

Download

 

 

 

 

 

 

 

 

Type = O2;

PKW: 1HEX=1

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r004

 

 

Output Amps

 

 

 

 

2 /

BR

 

 

 

 

 

AFE output current (fundamental r.m.s.)

 

 

[A]

 

 

 

 

 

4Hex

 

 

Note:

The displayed value corresponds to the current at

 

 

 

 

 

 

 

 

 

 

 

 

the inverter (CT). The line current at the AFE input

 

 

 

 

 

 

 

 

 

 

 

 

deviates from this value by the current component

 

 

 

 

 

 

 

 

 

 

 

 

which flows through the filter capacitor.

 

 

 

 

 

 

 

 

 

 

Analog output: 100 % with code number (PWE) = 4 * P072

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=0.1 A

PZD Gr.: 6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r006

 

 

DC Bus Volts

 

 

 

 

2 /

BR

 

 

 

 

 

Actual DC-link voltage value

 

 

[V]

 

 

 

 

 

6Hex

 

 

Display quantity for the PMU and OP.

 

 

 

 

 

 

 

 

 

 

Analog output: 100 % with code number (PWE) = 4*P071

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=I2;

 

PKW: 1HEX=1 V

PZD Gr.: 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r010

 

 

AFE utilization

 

 

 

 

2 / BR

 

 

AHex

 

 

Thermal AFE utilization as a result of an I2t calculation of the

 

[%]

 

 

 

 

 

 

 

output current.

 

 

 

 

 

 

 

 

 

 

 

 

Loading the AFE with maximum current for

 

 

 

 

 

 

 

 

 

 

 

30 seconds activates an alarm (P622) and for

 

 

 

 

 

 

 

 

 

 

60 seconds to a reduction in the load current to 91 % of

 

 

 

 

 

 

 

 

 

 

 

AFE rated current.

 

 

 

 

 

 

 

 

 

 

 

Analog output: 100 % with code number (PWE) = 16384 %

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1 %

PZD Group: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12-2

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE