Connecting-Up and Wiring

01.2004

 

 

7.4Connecting up control cables

NOTE

Generally, control lines that are connected to the AFE inverter must be

 

shielded to achieve maximum possible interference immunity. The

 

shield must be grounded at both ends.

 

To avoid noise coupling, control wires which are directly connected to

 

the chassis should be separated from power wiring by a minimum

 

distance of 20 cm.

 

Control and power cables must cross each other at an angle of 90°.

 

 

7.5Terminal assignments

X100 control

The terminals on the control terminal strip are as follows:

 

terminal strip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal

 

Name

 

Function

 

 

 

 

 

 

 

 

1

 

 

 

Transmit and receive line -RS485, differential input

 

 

 

 

 

 

 

 

 

 

 

 

/ output, positive (RS485/T+)

 

 

 

 

 

 

 

2

 

 

 

Transmit and receive line -RS485, differential input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

/ output, negative (RS485/T-)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

Transmit output RS485 Standard,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

differential output, positive (RS485T+)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

Transmit output RS485 Standard,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

differential output, negative (RS485T-)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 *)

 

M RS485

 

Reference potential RS485

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

Digital output 2, must be connected to VSB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

Digital output 2, must be connected to VSB

 

 

 

 

 

 

 

 

8 **)

 

 

 

Digital output 2, (changeover) NC contact

 

Possible cross-section: 1.5 mm2 (AWG 16)

In the assembled state, terminal 1 is at the top.

*) An identical interface to the type on connector -X100 is available on connector -X300 on the parameterizing unit. Only one of these two interfaces may be used, see Section "Interfaces".

Digital output 1 is available on -X9:4,5 (must be connected to precharging circuit / VSB)

**) Load capability of digital outputs: AC 60 V, 60 VA, cos ϕ = 1

AC 60 V, 16 VA, cos ϕ = 0.4 DC 60 V, 24 W

Table 7-6 Control terminal strip X100

7-12

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE