Faults and Alarms

 

 

 

 

 

 

01.2004

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fault messages

 

 

No.

 

 

Description of fault

 

 

 

Remedial measures

 

 

F006

 

DC-link overvoltage

 

 

 

 

Regenerative feedback power of the connected converter

 

 

 

 

The drive has been shut down due to an excessive DC-

 

 

is greater than that of the AFE.

 

 

 

 

 

 

Check the following parameters:

 

 

 

 

link voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P572 Source regeneration enable

 

 

 

 

Line voltage range

I

Shutdown threshold

 

 

 

 

 

 

 

 

 

P161 Max. generator current limit of AFE

 

 

 

 

380 V to 460 V

I

approx. 820 V

 

 

 

 

 

 

500 V to 575 V

I

approx. 1020 V

 

 

P173 Maximum current

 

 

 

 

660 V to 690 V

I

approx. 1220 V

 

 

 

 

 

 

 

F007

 

Electrical off

 

 

 

 

 

Check the external voltage supply

 

 

 

 

Failure of the electronic voltage supply -G10 in the mains

 

 

Check the wiring (hardware and software) for the ext.

 

 

 

 

connection module (external 24 V)

 

 

24 V monitoring function (software FS: 576 = 1004 =

 

 

 

 

 

 

 

 

 

 

digital input 4).

 

 

 

 

 

 

 

 

 

 

 

F008

DC-link undervoltage

 

 

 

 

Check

 

 

 

 

The DC-link voltage has dropped below the minimum limit

 

 

the main contactor control in cases where the fault

 

 

 

 

value (line supply voltage)

 

 

 

 

 

occurs immediately after precharging

 

 

 

 

 

 

 

 

 

 

P160 Maximum motor current limit

 

 

 

 

 

 

 

 

 

 

P173 Maximum current

 

 

F009

 

Supply failure

 

 

 

 

 

Check

 

 

 

 

The line voltage has remained below the undervoltage

 

 

the line voltage and line frequency

 

 

 

 

threshold (P074) for longer than the maximum line failure

 

 

Compare with

 

 

 

 

period (P155).

 

 

 

 

 

the threshold in Undervoltage threshold P074

 

 

 

 

The line failure fault is also activated if the line voltage

 

 

the maximum Line failure time P155

 

 

 

 

frequency drops below 40 Hz or exceeds 70 Hz.

 

 

the Line voltage P071

 

 

F011

 

Overcurrent

 

 

 

 

 

Check

 

 

 

 

The drive has been shut down as a result of overcurrent.

 

 

the main contactor control in cases where the fault

 

 

 

 

The trip threshold has been exceeded.

 

 

 

occurs immediately after precharging

 

 

 

 

 

 

 

 

 

 

the AFE output for short circuit or earth fault

 

 

F013

 

Overload

 

 

 

 

 

Check

 

 

 

 

The maximum current parameterized in P173 has been

 

 

the maximum current P173 IMaximum current

 

 

 

 

exceeded by more than 10% or the load in regenerative

 

 

the AFE load

 

 

 

 

feedback mode was so high that the DC-link voltage has

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reached its maximum value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F023

 

Inverter temp.

 

 

 

 

 

Measure inlet or ambient air temperature. Apply reduction

 

 

 

 

The inverter temperature has exceeded its maximum

 

 

curves when theta >40 ºC.

 

 

 

 

 

 

See section "Technical Data" in Operator's Guide

 

 

 

 

limit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r949 = 1 Inverter temperature limit is exceeded

 

 

Check

 

 

 

 

r949 = 2 Sensor 1: Break in sensor lead or sensor

 

 

whether fan -E1 is connected and/or rotating in the

 

 

 

 

 

defective

 

 

 

 

 

correct direction.

 

 

 

 

r949 = 18 Sensor 2: Break in sensor lead or sensor

 

 

the air inlet and outlet openings for dirt/blockage.

 

 

 

 

 

 

the temperature sensor connected to -X30

 

 

 

 

 

defective

 

 

 

 

 

 

 

 

r949 = 34 Sensor 3: Break in sensor lead or sensor

 

 

 

 

 

 

 

 

 

 

defective

 

 

 

 

 

 

 

 

 

 

 

r949 = 50 Sensor 4: Break in sensor lead or sensor

 

 

 

 

 

 

 

 

 

 

defective

 

 

 

 

 

 

 

 

 

F024

 

Overload precharging resistor

 

 

Check

 

 

 

 

Precharging resistor protection has responded during DC-

 

 

for high-resistance short circuit or earth fault during

 

 

 

 

link forming and automatic restart (WEA).

 

 

 

forming or WEA

 

 

 

 

Fault F024 occurs when IΙI > 1 % P072 for longer than

 

 

whether line voltage < 80 % during WEA

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5 P326.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14-2

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE