Faults and Alarms

 

 

 

 

 

 

01.2004

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fault messages

 

 

No.

 

 

Description of fault

 

 

 

Remedial measures

 

 

F006

 

DC-link overvoltage

 

 

 

 

Regenerative feedback power of the connected converter

 

 

 

 

The drive has been shut down due to an excessive DC-

 

 

is greater than that of the AFE.

 

 

 

 

 

 

Check the following parameters:

 

 

 

 

link voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

•

P572 Source regeneration enable

 

 

 

 

Line voltage range

I

Shutdown threshold

 

 

 

 

 

 

 

 

 

•

P161 Max. generator current limit of AFE

 

 

 

 

380 V to 460 V

I

approx. 820 V

 

 

 

 

 

 

500 V to 575 V

I

approx. 1020 V

 

 

•

P173 Maximum current

 

 

 

 

660 V to 690 V

I

approx. 1220 V

 

 

 

 

 

 

 

F007

 

Electrical off

 

 

 

 

 

Check the external voltage supply

 

 

 

 

Failure of the electronic voltage supply -G10 in the mains

 

 

Check the wiring (hardware and software) for the ext.

 

 

 

 

connection module (external 24 V)

 

 

24 V monitoring function (software FS: 576 = 1004 =

 

 

 

 

 

 

 

 

 

 

digital input 4).

 

 

 

 

 

 

 

 

 

 

 

F008

DC-link undervoltage

 

 

 

 

Check

 

 

 

 

The DC-link voltage has dropped below the minimum limit

 

 

• the main contactor control in cases where the fault

 

 

 

 

value (≈ line supply voltage)

 

 

 

 

 

occurs immediately after precharging

 

 

 

 

 

 

 

 

 

 

•

P160 Maximum motor current limit

 

 

 

 

 

 

 

 

 

 

•

P173 Maximum current

 

 

F009

 

Supply failure

 

 

 

 

 

Check

 

 

 

 

The line voltage has remained below the undervoltage

 

 

• the line voltage and line frequency

 

 

 

 

threshold (P074) for longer than the maximum line failure

 

 

Compare with

 

 

 

 

period (P155).

 

 

 

 

 

•

the threshold in Undervoltage threshold P074

 

 

 

 

The line failure fault is also activated if the line voltage

 

 

•

the maximum Line failure time P155

 

 

 

 

frequency drops below 40 Hz or exceeds 70 Hz.

 

 

•

the Line voltage P071

 

 

F011

 

Overcurrent

 

 

 

 

 

Check

 

 

 

 

The drive has been shut down as a result of overcurrent.

 

 

• the main contactor control in cases where the fault

 

 

 

 

The trip threshold has been exceeded.

 

 

 

occurs immediately after precharging

 

 

 

 

 

 

 

 

 

 

•

the AFE output for short circuit or earth fault

 

 

F013

 

Overload

 

 

 

 

 

Check

 

 

 

 

The maximum current parameterized in P173 has been

 

 

•

the maximum current P173 IMaximum current

 

 

 

 

exceeded by more than 10% or the load in regenerative

 

 

•

the AFE load

 

 

 

 

feedback mode was so high that the DC-link voltage has

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reached its maximum value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F023

 

Inverter temp.

 

 

 

 

 

Measure inlet or ambient air temperature. Apply reduction

 

 

 

 

The inverter temperature has exceeded its maximum

 

 

curves when theta >40 ºC.

 

 

 

 

 

 

See section "Technical Data" in Operator's Guide

 

 

 

 

limit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r949 = 1 Inverter temperature limit is exceeded

 

 

Check

 

 

 

 

r949 = 2 Sensor 1: Break in sensor lead or sensor

 

 

• whether fan -E1 is connected and/or rotating in the

 

 

 

 

 

defective

 

 

 

 

 

correct direction.

 

 

 

 

r949 = 18 Sensor 2: Break in sensor lead or sensor

 

 

•

the air inlet and outlet openings for dirt/blockage.

 

 

 

 

 

 

•

the temperature sensor connected to -X30

 

 

 

 

 

defective

 

 

 

 

 

 

 

 

r949 = 34 Sensor 3: Break in sensor lead or sensor

 

 

 

 

 

 

 

 

 

 

defective

 

 

 

 

 

 

 

 

 

 

 

r949 = 50 Sensor 4: Break in sensor lead or sensor

 

 

 

 

 

 

 

 

 

 

defective

 

 

 

 

 

 

 

 

 

F024

 

Overload precharging resistor

 

 

Check

 

 

 

 

Precharging resistor protection has responded during DC-

 

 

• for high-resistance short circuit or earth fault during

 

 

 

 

link forming and automatic restart (WEA).

 

 

 

forming or WEA

 

 

 

 

Fault F024 occurs when IΙI > 1 % P072 for longer than

 

 

•

whether line voltage < 80 % during WEA

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5 ⋅ P326.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14-2

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 133
Image 133
Siemens 400 V / 210...590 A operating instructions 14-2