Installation

 

 

5 Installation

5.1Installing the units

WARNING

Safe converter operation requires that the equipment is mounted and

 

commissioned by qualified personnel taking into account the warning

 

information provided in these Operating Instructions.

 

The general and domestic installation and safety regulations for work

 

on electrical power equipment (e.g. VDE) must be observed as well as

 

the professional handling of tools and the use of personal protective

 

equipment.

 

Death, severe bodily injury or significant material damage could result if

 

these instructions are not followed.

 

 

Clearances

When you position the AFE inverter, make sure that the DC link

 

connection is on the upper side of the unit and the AFE reactor

 

connection is on the bottom side of the unit.

 

The AFE basic mains module and the CleanPower filter must always be

 

mounted vertically (never sideways).

 

To ensure a free flow of cooling air when components are installed in a

 

control cabinet, they must be mounted at a distance of 350 mm from

 

the base (for air inlet) and 350 mm from the reflective cabinet ceiling

 

(for air outlet).

 

The cabinet ventilation system must be dimensioned according to the

 

level of heat loss. Further information can be found in the technical

 

data.

Requirements at the

Foreign particles

point of installation

The units must be protected against the ingress of foreign particles

 

as otherwise their function and operational safety cannot be

 

ensured.

 

Dust, gases, vapors

 

Equipment rooms must be dry and dust-free. Ambient and cooling

 

air must not contain any electrically conductive gases, vapors and

 

dusts which could diminish the functionality. If necessary, filters

 

should be used or other corrective measures taken.

 

Ambient climate

 

The built-in units must only be operated in an ambient climate

 

conforming to DIN IEC 721-3-3 Class 3K3. Derating will be required

 

with cooling air temperatures of more than 40 °C (104 °F) and

 

installation altitudes above 1000 m to ensure adequate cooling of

 

the AFE inverter.

Siemens AG 6SE7087-6CX86-2BA1

5-1

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 19