Control and Status Words

 

 

Bit 11: Reserved

Bit 12: Regenerative feedback enable command (H "Regenerative feedback enable")

Condition

HIGH signal

Result

Regenerative feedback operation is enabled.

 

 

Bit 13: Reserved

 

 

 

Bit 14: Reserved

 

Bit 15: External fault 1 command (L "External fault 1")

Condition

LOW signal

Result

FAULT (007) and fault message (F035).

 

The inverter pulses are inhibited and the main contactor opened.

 

See Section "Fault and alarm messages"

Bit 16: Monitoring of external 24 V voltage supply (L "24V not o.k." / H "24V o.k.")

Condition

LOW signal

Result

Alarm A039 in operating states STARTING LOCKOUT (008) and

 

READY FOR ON (009).

 

Fault F007 in operating states PRECHARGING (010), READY TO

 

RUN (011) and RUN (014).

 

 

Bit 17: Reserved

 

Bit 18: Reserve data set RDS bit 0 command (L "RDS1" / H "RDS2")

Condition

READY FOR ON (009), PRECHARGING (010) or READY TO RUN

 

(011)

 

A HIGH signal activates RDS2, and a LOW signal RDS1.

Result

The parameter settings of the appropriate reserve data set in the

 

setpoint channel and closed-loop/open-loop control are activated.

 

See Section "Function diagrams".

 

 

Bit 19: Reserved

 

 

 

Bit 20: Reserved

 

Siemens AG 6SE7087-6CX86-2BA1