01.2004

Control and Status Words

 

 

Bit 23: "AFE overtemperature fault" signal (H)

HIGH signal

"Inverter temperature too high" fault (F023)

Meaning

The inverter temperature limit value has been exceeded.

 

See Section "Fault and alarm messages".

 

Output at terminal strip (CUSA, SCB1) with L signal.

Bit 24: "AFE overtemperature alarm" signal (H)

HIGH signal

"Inverter temperature too high" alarm (A022)

Meaning

Alarm-tripping temperature threshold of inverter has been exceeded.

 

See Section "Fault and alarm messages".

 

Output at terminal strip (CUSA, SCB1) with L signal

 

 

Bit 25: Reserved

 

 

 

Bit 26: Reserved

 

 

 

Bit 27: Reserved

 

 

 

Bit 28: Reserved

 

Bit 29: "PC energized" signal (H)

HIGH signal

The precharging contactor is energized.

WARNING

 

The status bit is always connected to terminal -X9 on the AFE. A

 

different wiring is not possible and is also not allowed because the AFE

 

inverter might be destroyed if the main contactor is activated before the

 

DC link has been precharged.

 

 

Bit 30: Reserved

 

 

Bit 31: "Precharging active" signal (H)

HIGH signal

PRECHARGING state (010)

Meaning

The DC link is precharged as soon as an ON command is issued.

Siemens AG 6SE7087-6CX86-2BA1

13-21

SIMOVERT MASTERDRIVES AFE Operating Instructions