Faults and Alarms

01.2004

 

 

14.2Alarms

 

 

 

 

 

 

 

An alarm message is periodically displayed on the PMU by A=alarm

 

 

 

 

 

 

 

 

and a 3-digit number. An alarm cannot be acknowledged. It is

 

 

 

 

 

 

 

 

automatically deleted once the cause has been removed. Several

 

 

 

 

 

 

 

 

alarms can be active simultaneously, in which case they are displayed

 

 

 

 

 

 

 

 

one after another.

 

 

 

 

 

 

 

 

 

 

 

 

If the AFE inverter is operated with the OP1S control panel, the warning

 

 

 

 

 

 

 

 

is displayed in the bottom line of the operation display. The red LED

 

 

 

 

 

 

 

 

also flashes (refer to the OP1S Operating Instructions).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm messages

 

 

Alarm

 

 

Param-

 

 

Description

 

 

 

Remedial measures

 

 

No.

 

 

No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit No.

 

 

 

 

 

 

 

 

 

A001

 

 

P953

 

 

Comp. time

 

 

Check r725 Available computation time.

 

 

 

 

 

 

 

 

CU board comp. time utilization too high

 

 

Increase P308 Sampling time

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A015

 

 

P953

 

 

Ext. alarm 1

 

 

External alarm is active. Check whether the lead to

 

 

 

 

 

 

 

 

Parameterizable, external alarm input 1

 

 

the appropriate digital input is interrupted.

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

has been activated

 

 

Check parameter P588 Src No Ext Warn1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See section "Digital inputs" in Operator's Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A016

 

 

P953

 

 

Ext. alarm 2

 

 

External alarm is active. Check whether the lead to

 

 

 

 

 

 

 

 

Parameterizable, external alarm input 2

 

 

the appropriate digital input is interrupted.

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

has been activated

 

 

Check parameter P589 Src No Ext Warn2.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See section "Digital inputs" in Operator's Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A020

 

 

P954

 

 

Overcurrent

 

 

Check the driven load for an overload condition.

 

 

 

 

 

 

 

 

An overcurrent has been detected.

 

 

Are the dynamic requirements too high?

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A021

 

 

P954

 

 

Overvoltage

 

 

Check the line voltage.

 

 

 

 

 

 

 

A DC-link overvoltage condition has been detected.

 

 

Are the dynamic requirements too high?

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A022

 

 

P954

 

 

Inv.temp.

 

 

Check r011 AFE temperature.

 

 

 

 

 

 

 

 

The alarm activation threshold has been exceeded.

 

 

Measure inlet or ambient air temperature. Apply

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

reduction curves when theta >40 ºC.

 

 

 

 

 

 

 

 

 

 

 

See section "Technical Data" in Operator's Guide

 

 

 

 

 

 

 

 

 

 

 

Check

 

 

 

 

 

 

 

 

 

 

 

whether fan -E1 is connected and/or rotating in

 

 

 

 

 

 

 

 

 

 

 

 

the correct direction.

 

 

 

 

 

 

 

 

 

 

 

the air inlet and outlet openings for dirt/blockage.

 

 

 

 

 

 

 

 

 

 

 

the temperature sensor connected to -X30

 

 

A025

 

 

P954

 

 

I2t- inv.

 

 

Check whether the rated output current or peak

 

 

 

 

 

 

 

 

The inverter will be thermally overloaded if it

 

 

current (operating class II) is (was) too high.

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

continues to operate under the current load

 

 

Check r010 AFE Utilization

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

conditions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14-6

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 137