Siemens 400 V / 210...590 A Replacing the capacitor battery, Capacitor battery weighs up to 30 kg

Models: 400 V / 210...590 A

1 166
Download 166 pages 35.09 Kb
Page 144
Image 144

01.2004

Maintenance

 

 

15.2.4Replacing the capacitor battery

The unit is an assembly which consists of the DC link capacitors, the capacitor support and the DC link bus module.

Construction type G Remove the terminal for the balancing resistor (cable eye M6). Undo the mechanical mounting.

Swing the capacitor battery out forwards and lift the unit at an angle of 45 ° out of the converter.

Construction type J The capacitor battery comprises three assemblies. Each assembly contains a capacitor support and a DC link bus module.

Undo the plug-in connections

Undo the mechanical fastening (three screws: Two left, one right)

Swing the capacitor sideways until it reaches the limit stop, lift the unit slightly and pull it forwards out of the converter.

CAUTION

The capacitor battery weighs up to 30 kg!

 

 

Siemens AG 6SE7087-6CX86-2BA1

15-5

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 144
Image 144
Siemens 400 V / 210...590 A operating instructions Replacing the capacitor battery, Capacitor battery weighs up to 30 kg