Control and Status Words

01.2004

 

 

13.2.3Description of the status word bits

Bit 0: "Ready for ON" signal (H)

HIGH signal

STARTING LOCKOUT (008) or READY FOR ON (009) state

Meaning

The power supply, open-loop control and closed-loop control are all

 

operative.

 

The inverter pulses are inhibited.

Bit 1: "Ready to Run" signal (H)

HIGH signal

PRECHARGING (010) or READY TO RUN (011) state

Meaning

The power supply, open-loop control and closed-loop control are all

 

operative.

 

The converter is switched on.

 

Precharging has been completed.

 

The AFE inverter pulses are disabled and Ud control is disabled.

Bit 2: "Run" signal (H)

HIGH signal

RUN state (014)

Meaning

The converter is in operation.

 

The AFE inverter pulses are enabled.

 

Ud control is in operation.

Bit 3: "Fault" signal (H)

HIGH signal

FAULT state (007)

Meaning

A fault (fault type irrelevant) has occurred.

 

Output at terminal strip (CUSA, TSY, SCI1/2) with L signal.

 

Bit 4: "OFF2" signal (L)

LOW signal

OFF2 command is active

Meaning

An OFF2 command (control word bit 1) has been issued.

Bit 5: Reserved

13-18

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE