Description

01.2004

 

 

Operating principle On the 3-phase end, a mains angle-oriented high-speed vector control is subordinate to the DC link voltage control and impresses an almost sinusoidal current on the network so as to minimize system perturbations with the aid of the subsequently connected Clean Power filter.

The vector control also enables setting of the power factor cos phi, and thus reactive power compensation, but the operating current requirement has priority.

The VSB module (Voltage Sensing Board), functions as the network angle sensor, similarly to the principle of an encoder.

For safety reasons, an AFE rectifier/regenerative feedback unit must be connected to the mains via a main contactor; see Fig. 2-1. For this reason, an external 24 V power supply is always required to feed the VSB board and the AFE inverter.

 

 

 

6

 

 

 

 

 

 

 

 

 

VSB

 

 

CUSA

 

Precharging contactor

 

 

 

 

 

RV

 

 

 

 

 

 

 

 

 

 

 

Line supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C / L+

L1, L2, L3

 

 

 

 

 

 

 

U2

 

 

DC units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connection

 

 

 

 

 

 

 

 

 

 

W2

 

 

Main contactor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D / L -

 

 

 

 

 

 

 

 

 

 

 

 

 

PE

 

CF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Precharging and main contactor

CleanPower filter AFE reactor

 

AFE inverter with CUSA

 

 

 

 

 

 

 

 

 

 

 

 

and fuses

 

 

Fig. 2-1

Basic circuit

 

 

 

 

2-2

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE