Parameterization

 

 

11.2.3Initialization (MLFB input) (P052 = 2)

Function

Condition

Result

P051 = 3

P052 = 2

P070 =

This function is used to alter the order number (device type) of the converter.

"Initialization" can be selected in operating states CONTROL SETTINGS (005), FAULT (007), STARTING LOCKOUT (008) or READY FOR ON (009).

When the order number is changed, only some parameters are reset to their factory values (shipped status of converter) as a function of the new order number. The process data connection remains unchanged.

Access level "Expert Mode"

(to change P070)

Select Initialization

Specify MLFB

(= Order No. of the AFE inverter, see rating plate)

When the CU board is changed, the appropriate MLFB for the converter must be entered. When setting parameters via PMU, enter the corresponding code number (PWE) according to the table below.

Rated voltage 3 AC 380 V (-20 %) to 460 V (+5 %)

Order number

Type power

Rated current

PWE

6SE70..

[kW]

[A]

 

 

 

 

 

32-1EG80

110

210

103

 

 

 

 

32-6EG80

132

260

109

 

 

 

 

33-2EG80

160

315

113

 

 

 

 

33-7EG80

200

370

117

 

 

 

 

35-1EJ80

250

510

120

 

 

 

 

36-0EJ80

315

560

123

 

 

 

 

37-0EJ80

400

656

126

 

 

 

 

Siemens AG 6SE7087-6CX86-2BA1

11-7

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 67