01.2004

 

 

 

 

 

 

 

 

 

Parameter List

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PNU

 

Parameter Name in OP1

 

 

Range

 

# of Indices

 

read:

_/_

 

 

 

 

 

 

 

 

 

[Unit]

 

Factory

 

write:

_/_

 

*:conf-P

 

Description

 

 

 

 

Value Texts

 

Settings

 

 

 

 

 

 

P690

 

SCB Act Values

 

 

 

 

0 to 999

16

 

3 /

BR

 

 

 

*

 

Output of actual values via the serial interface of the SCB board

 

 

i001=0

 

3 /

BR

 

 

 

2B2Hex

 

Defines which parameter must be transferred

at which telegram

 

 

i002=0

 

 

 

 

 

 

 

 

position.

 

 

 

 

 

 

 

i003=0

 

 

 

 

 

 

 

 

Notes:

Status word 1 (r968) should be assigned to

 

 

i004=0

 

 

 

 

 

 

 

 

 

word 1.

 

 

 

 

 

i005=0

 

 

 

 

 

 

 

 

 

In the case of double word parameters (type I4),

 

 

i006=0

 

 

 

 

 

 

 

 

 

 

 

i007=0

 

 

 

 

 

 

 

 

 

the associated parameter number must be

 

 

 

 

 

 

 

 

 

 

 

 

 

i008=0

 

 

 

 

 

 

 

 

 

entered in two consecutive words or else only the

 

 

 

 

 

 

 

 

 

 

 

 

 

i009=0

 

 

 

 

 

 

 

 

 

most significant word will be transferred.

 

 

 

 

 

 

 

 

 

 

 

 

 

i010=0

 

 

 

 

 

 

 

 

 

The length (number of words) of the process data

 

 

 

 

 

 

 

 

 

 

 

 

 

i011=0

 

 

 

 

 

 

 

 

 

section in the telegram is set via P685, index i002.

 

 

 

 

 

 

 

 

 

 

 

 

 

i012=0

 

 

 

 

 

 

 

 

Indices: i001 =

W01: Word 01 of (process data section)

 

 

 

 

 

 

 

 

 

 

 

 

i013=0

 

 

 

 

 

 

 

 

 

 

 

of the telegram

 

 

 

i014=0

 

 

 

 

 

 

 

 

i002 = W02: Word 02 of (process data section)

 

 

i015=0

 

 

 

 

 

 

 

...

 

 

of the telegram

 

 

 

i016=0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i016 =

W16: Word 16 of (process data section)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of the telegram

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION:

When P682 = 3 (peer-to-peer protocol), a

 

 

 

 

 

 

 

 

 

 

 

 

maximum of 5 words can be transferred (i001 to

 

 

 

 

 

 

 

 

 

 

 

 

i005).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1.0

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P694

 

CB/TB Act Values

 

 

 

0 to 999

16

 

3 /

BR

 

 

 

*

 

Output of actual values via CB or TB

 

 

 

i001=968

 

3 /

BR

 

 

 

2B6Hex

 

Defines which parameter must be transferred

at which telegram

 

 

i002=0

 

 

 

 

 

 

 

 

position.

 

 

 

 

 

 

 

i003=0

 

 

 

 

 

 

 

 

Notes:

Status word 1 (r968) should be assigned to

 

 

i004=0

 

 

 

 

 

 

 

 

 

word 1.

 

 

 

 

 

i005=0

 

 

 

 

 

 

 

 

 

In the case of double word parameters (type I4),

 

 

i006=0

 

 

 

 

 

 

 

 

 

 

 

i007=0

 

 

 

 

 

 

 

 

 

the associated parameter number must be

 

 

 

 

 

 

 

 

 

 

 

 

 

i008=0

 

 

 

 

 

 

 

 

 

entered in two consecutive words or else only the

 

 

 

 

 

 

 

 

 

 

 

 

 

i009=0

 

 

 

 

 

 

 

 

 

most significant word will be transferred.

 

 

 

 

 

 

 

 

 

 

 

 

 

i010=0

 

 

 

 

 

 

 

 

Indices: i001=

W01:

Word 01 of (process data section)

 

 

 

 

 

 

 

 

 

 

 

 

i011=0

 

 

 

 

 

 

 

 

 

 

 

of the telegram

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i012=0

 

 

 

 

 

 

 

 

i002=

W02:

Word 02 of (process data section)

 

 

 

 

 

 

 

 

 

 

 

 

i013=0

 

 

 

 

 

 

 

 

 

 

 

of the telegram

 

 

 

 

 

 

 

 

 

 

...

 

 

 

 

 

i014=0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i015=0

 

 

 

 

 

 

 

 

i016=

W16:

Word 16 of (process data section)

 

 

 

 

 

 

 

 

 

 

 

 

i016=0

 

 

 

 

 

 

 

 

 

 

 

of the telegram

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1.0

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

P695

 

CB/TB TlgOFFTime

 

 

 

0 to 6500

 

 

3 /

BR

 

 

 

*

 

Telegram failure time for CB and TB

 

[ms]

10

 

3 /

BR

 

 

 

2B7Hex

 

Shutdown on faults occurs if no correct telegram is received

 

 

 

 

 

 

 

 

 

 

 

within the specified time.

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting instructions:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value 0:

No monitoring and no fault shutdown;

 

 

 

 

 

 

 

 

 

 

 

 

parameterize for sporadic (acyclic) telegrams.

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1.0 ms

PZD: 4000HEX=1638.4 ms

 

 

 

 

 

 

 

 

Siemens AG 6SE7087-6CX86-2BA1

12-29

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 99
Image 99
Siemens 400 V / 210...590 A operating instructions 12-29, P694 CB/TB Act Values, P695 CB/TB TlgOFFTime