01.2004

 

 

 

 

 

 

 

Faults and Alarms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fault messages

 

 

 

 

No.

 

Description of fault

 

 

 

Remedial measures

 

 

F076

 

Aninput1 SL2

 

 

 

Check connection from signal source to SCI1

 

 

 

 

Amps at analog input 1, slave2, have dropped below 4mA

 

 

(slave1) -X428:4, 5.

 

 

 

 

F077

 

Aninput2 SL2

 

 

 

Check connection from signal source to SCI1

 

 

 

 

Amps at analog input 2, slave2, have dropped below 4mA

 

 

(slave 2) -X428:7,8.

 

 

 

 

F078

 

Aninput3 SL2

 

 

 

Check connection from signal source to SCI1

 

 

 

 

Amps at analog input 3, slave2, have dropped below 4mA

 

 

(slave 3) -X428:10, 11.

 

 

 

 

F079

 

SCB telegram

 

 

 

Check the connections of the SCB1(2).

 

 

 

 

A telegram has not been received from the SCB (USS,

 

 

Check P687.01"SCom/SCB TlgOFF".

 

 

 

 

peer-to-peer, SCI) within the telegram failure time.

 

 

Replace the SCB1(2).

 

 

 

 

 

 

 

 

 

 

Replace the CU (-A10).

 

 

 

 

 

 

 

 

 

 

 

 

 

F080

 

TB/CB init.

 

 

 

r949 = 1 TB/CB not inserted or TB/CB board code

 

 

 

 

Board initialization error at the DPR interface

 

 

incorrect

 

 

 

 

 

 

 

 

r949 = 2 TB is not compatible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r949 = 3 CB is not compatible

 

 

 

 

 

 

 

 

r949 = 5 Error in initialization data

 

 

 

 

 

 

 

 

Check contacts on the T300 / CB board and whether the

 

 

 

 

 

 

 

 

board slot matches the appropriate parameter setting;

 

 

 

 

 

 

 

 

P090 Board Position 2,

P091 Board Position 3

 

 

 

 

 

 

 

 

r723 PCB Code,

r724 PCB Code

 

 

 

 

 

 

 

 

r949 = 6 Timeout during initialization

 

 

 

 

 

 

 

 

r949 = 10 Error in configuration channel

 

 

 

 

 

 

 

 

Check the CB initialization parameters;

 

 

 

 

 

 

 

 

P918 CB Bus Address,

 

 

 

 

 

 

 

 

 

 

696 to P705 CB Parameters 1 to 10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F081

 

TB/CB heartb.

 

 

 

Replace the TB or CB

 

 

 

 

 

 

TB or CB is no longer processing the monitoring counter

 

 

Check the connection between the subrack and option

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F082

 

TB/CB Tlgr.

 

 

 

Check the connections of the CB/TB.

 

 

 

 

No new process data have been received from the TB or

 

 

Check P695 "CB/TB TlgOFFTime".

 

 

 

 

CB within the telegram failure time.

 

 

 

Replace the CB.

 

 

 

 

 

 

 

 

 

 

Replace the TB.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F091

Form.interrupt

 

 

 

Depending on the fault

 

 

 

 

 

 

Forming of the DC link has been interrupted.

 

 

Line voltage too low or incorrect line voltage (P071)

 

 

 

 

 

 

 

 

 

 

 

 

r949 = 1 Abortion due to another fault

 

 

 

parameterized

 

 

 

 

 

 

r949 = 2 Abortion because Vd too low

 

 

OFF command

 

 

 

 

 

 

r949 = 3 Abortion by OFF command

 

 

 

 

 

 

 

 

 

 

No ON command

 

 

 

 

 

 

r949 = 4 Abortion because no ON command within 20 s

 

 

 

 

 

 

 

 

of forming function selection

 

 

 

 

 

 

 

 

F255

 

Fault in NOVRAM

 

 

 

Switch the device off and then on again.

 

 

 

 

 

 

 

 

Replace the CU if the fault occurs again.

 

 

 

 

Table 14-1

Fault numbers, causes and their counter-measures

 

 

 

Siemens AG 6SE7087-6CX86-2BA1

14-5

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 136
Image 136
Siemens 400 V / 210...590 A operating instructions 14-5