Control and Status Words

01.2004

 

 

13.2Status word

Introduction and

Status words are process data as defined by the explanation in Section

example of

"Process data".

application

A "destination" at which the bit status can be identified (digital outputs

 

of CUSA, SCI 1/2 terminals, TSY terminals) can be parameterized for

 

each bit in a status word.

 

One parameter is available for "wiring up" the destination for each

 

status bit.

 

 

As shown below, the selection parameters have three indices:

 

Index i001

Selection of a terminal on the CUSA / PEU board

 

 

(basic unit)

 

Index i002

Selection of a terminal on the SCI 1/2 board (option)

 

Index i003

Selection of a terminal on the TSY board (option)

Example of wiring to The message "motor operation" (status word 1, bit 14) must be "wired

a destination

up" to digital output 3 (BA3) on the CUSA (terminal X102:29/33) as a

 

 

 

high-active signal:

 

 

 

 

 

 

"Wiring" of a status bit to a digital output on the CUSA is

 

 

 

 

parameterized via index i001.

 

 

 

 

 

The table for status word 1 indicates that the message "Motor

 

 

 

 

operation" is assigned to parameter P614.

 

 

 

Look for the parameter value for the desired destination in the same

 

 

 

 

table. The result is 1003 for digital output 3 on the CU.

 

 

 

This parameter value must now be set in parameter P614.1.

 

 

 

 

 

 

 

 

 

 

Bit #

Meaning

 

 

Parameter

Parameter value

Desired destination connection

 

 

 

 

 

 

 

 

 

 

Bit 14

Motor operation

 

P614.1

1003

BA3 terminal -X102:29/33

 

 

 

 

 

 

 

 

 

 

 

 

When a High signal is applied to terminal -X102:29/33, the AFE

 

 

 

operates in generator mode and, in the case of a Low signal, in motor

 

 

 

mode.

 

 

 

 

 

 

If a value assigned to a terminal (digital output BA) is allocated to a

 

 

 

destination once in a selection parameter, then it will not be available in

 

 

 

the same index of any other selection parameter as a terminal is only

 

 

 

suitable for the output of one status bit.

NOTE

 

 

 

Faults, alarms and starting lockout (HIGH active) are displayed as

 

 

 

LOW active via the terminal strip (digital outputs).

 

 

 

This also applies to any option boards!

See Section "Digital outputs".

13.2.1Status word 1 (visualization parameter r552 or r968)

PMU display "Status word 1"

15

14

7

6

13

12

5

4

11

10

3

2

9

8

1

0

13-14

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 124
Image 124
Siemens 400 V / 210...590 A Status word 1 visualization parameter r552 or r968, Destination, PMU display Status word