01.2004

Control and Status Words

 

 

13.1.2Control word 1 (visualization parameter r550 or r967)

The factory setting applies only when P077 = 0.

Designation

High / Low values

Parameter No.

Fact. setting

Possible

Bit No. (meaning)

(1 = High, 0 = Low)

GRD (RES)

GRD (RES)

sources

 

 

 

 

(P077 = 0)

see 8.1.4

 

 

 

 

 

ON / OFF1 (stop)

ON

OFF1

 

 

 

 

0

1

0

 

P554.1 (2)

1010 (1001)

Tab. X,A

 

 

 

 

 

 

OFF2 (electrical)

ON

OFF2

 

 

 

 

 

 

 

&

P555.1 (2)

0001 (1002)

Tab. X,B

1

1

0

P556.1 (2)

0001 (0001)

Tab. X,B

 

 

 

 

 

 

 

 

 

 

P557.1 (2)

0001 (0001)

Tab. X,B

2

Reserved

 

 

 

 

 

 

 

 

 

 

Inverter enable

Enabled

Inhibited

 

 

 

 

3

1

0

 

P561.1 (2)

0001 (0001)

Tab. X,F

 

 

 

 

 

 

4

Reserved

 

 

 

 

 

 

 

 

 

 

5

Reserved

 

 

 

 

 

 

 

 

 

 

6

Reserved

 

 

 

 

 

 

 

 

 

 

Acknowledge

 

ON

 

 

 

 

 

 

 

 

P565.1 (2)

0000 (1003)

Tab. X,C

7

 

1

 

P566.1 (2)

0000 (0000)

Tab. X,C

 

 

 

 

 

 

 

 

 

 

0

 

 

P567.1 (2)

2001 (2001)

Tab. X,C

 

 

 

 

 

1010 (fixed)

 

Inching 1 1)

Inching 1 ON

Inching 1 OFF

 

 

 

 

8

1

0

 

P568.1 (2)

0000 (0000)

Tab. X,C

 

 

 

 

 

 

Inching 2 1)

Inching 2 ON

Inching 2 OFF

 

 

 

 

9

1

0

 

P569.1 (2)

0000 (0000)

Tab. X,C

 

 

 

 

 

 

PZD control by PLC

Control

No control

 

 

 

 

 

 

 

1

 

SCom1/2

 

10

1

0

 

CB / TB

 

 

 

 

 

 

SCB 2

 

11

Reserved

 

 

 

 

 

 

 

 

 

 

12

Reserved

 

 

 

 

 

 

 

 

 

 

13

Reserved

 

 

 

 

 

 

 

 

 

 

14

Reserved

 

 

 

 

 

 

 

 

 

 

External fault 1

No fault

External fault 1

 

 

 

 

15

1

0

 

P575.1 (2)

0001 (0001)

Tab. X,D

 

 

 

 

 

 

1) There is no inching setpoint 1 or inching setpoint 2 on the AFE

Siemens AG 6SE7087-6CX86-2BA1

13-3

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 113
Image 113