01.2004

Forming

 

 

16 Forming

For units in the 400 V and 690 V voltage classes (cf. 9th digit of the MLFB, letter E or H), the DC link capacitors must be formed again after an idle period of more than 2 years.

For units in the 500 V voltage class (cf. 9th digit of the MLFB, letter F), the DC link capacitors must be formed again after an idle period of more than 1 year.

If this is not carried out, the unit can be damaged when the line voltage is powered up.

If the unit was started-up within one year after having been manufactured, the DC link capacitors do not have to be re-formed. The date of manufacture of the unit can be read from the serial number.

How the serial

(Example: A-J60147512345)

number is made up

 

 

 

 

 

Digit

Example

Meaning

 

 

 

 

 

 

 

 

 

1 and 2

A-

Place of manufacture

 

3

M

2000

 

 

 

N

2001

 

 

 

P

2002

 

 

 

R

2003

 

 

 

S

2004

 

 

 

T

2005

 

4

1 to 9

January to September

 

 

 

O

October

 

 

 

N

November

 

 

 

D

December

 

 

5 to 14

 

Not relevant for forming

6 Forming time in hours

5

4

3

2

1

 

 

 

V

 

 

 

 

 

 

0

 

 

 

V

0

 

 

 

 

5

 

 

 

 

0

 

 

 

 

 

9

 

 

 

 

 

6

 

 

 

 

 

/

 

 

 

 

 

 

V

 

 

 

 

 

0

 

 

 

 

0

 

 

 

 

 

4

 

 

 

 

 

 

Off-circuit idle

 

 

 

 

 

 

 

time in years

1

2

3

4

5

Fig. 16-1 Forming time depending on the idle time of the AFE inverter

Siemens AG 6SE7087-6CX86-2BA1

16-1

SIMOVERT MASTERDRIVES AFE Operating Instructions