Connecting-Up and Wiring

01.2004

 

 

7.6Digital inputs/outputs

Digital inputs

Four parameterizable digital inputs (24 V) are available on the

 

control terminal strip (-X101) of the CUSA board. These inputs can be

 

used to input commands, external faults/alarms and for returning status

 

data to the AFE inverter's control word.

 

 

 

 

Connection:

See Section "Connecting up control cables".

 

Parameterization: See Section "Control and status words".

 

Factory setting (valid for standby operation):

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital

 

 

Command

 

Control

Parameter

 

input

 

HIGH

 

 

LOW

 

word bit

 

 

1

ON

 

 

 

OFF1

0

P554.2 = 1001

 

 

 

 

 

 

 

 

 

(standby)

 

2

ON

 

 

 

OFF2 (electrical)

1

P555.2 = 1002

 

 

 

 

 

 

 

 

 

(standby)

 

3

Acknowledge

 

 

 

7

P565.2 = 1003

 

 

 

 

 

 

 

(standby)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Standby setting

Basic setting

30

P590 = 1005

Table 7-10 Digital inputs

Digital outputs

Digital outputs 1 and 2 on the AFE inverter are pre-wired for the

 

precharging and main contactors. For safety reasons, they cannot be

 

wired up for other purposes.

 

 

 

 

 

 

Two further digital outputs are available for optional functions.

 

 

 

Factory setting:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital

Connector

Pin

 

Signal

Status

Para-

 

 

output

 

 

HIGH

 

LOW

word bit

meter

 

 

3

-X102

29

 

 

Fault

3

603.1

 

 

 

 

 

 

 

 

 

 

= 1003

 

 

 

4

-X102

32

 

 

Operation

2

602.1

 

 

 

 

 

 

 

 

 

 

= 1004

 

 

Table 7-11

Digital outputs

 

 

 

 

 

NOTE

 

 

Faults, alarms and starting lockout (HIGH active) are displayed as

 

LOW active via the terminal strip (digital outputs). See Section

 

 

 

"Status word".

 

 

 

 

 

 

 

7-16

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE