Page 76
Image 76

Parameter List

01.2004

 

 

12.3Drive data

 

PNU

 

 

Parameter Name in OP1

 

 

 

Range

 

# of Indices

 

read:

_/_

 

 

 

 

 

 

 

 

 

 

[Unit]

 

Factory

 

write:

_/_

 

*:conf-P

 

 

Description

 

 

 

 

Value Texts

 

Settings

 

 

 

 

 

 

P070

 

 

MLFB(6SE70..)

 

 

 

 

0 to 255

 

 

3

/U BR

 

*

 

 

MLFB (order number) of basic unit

 

 

 

 

0

 

3

/U

 

 

46Hex

 

 

For parameter values, see Section "Initialization"

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

 

PKW: 1HEX=1

 

PZD Gr.: -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P071

 

 

Line volts

 

 

 

 

 

90 to 1320

 

 

2

/ ABR

 

 

47Hex

 

 

Line supply voltage for AFE (r.m.s. of line-to-line voltage)

 

[V]

 

 

2

/

A

 

 

 

 

 

This parameter specifies the incoming AC supply voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

It is used to calculate the setpoint DC link voltage (P125) and

 

 

 

 

 

 

 

 

 

 

 

 

 

the thresholds for fault messages "Line supply overvoltage",

 

 

 

 

 

 

 

 

 

 

 

 

 

"Line supply undervoltage" (P074) and "DC link undervoltage".

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

 

PKW: 1HEX=1 V

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

P072

 

 

AFE current(n)

 

 

 

 

4.0 to 6540.0

 

 

2

/U ABR

 

48Hex

 

 

AFE rated output current

 

 

 

[A]

 

 

4

/U

 

 

 

 

 

Type=O2;

 

PKW: 1HEX=0.1 A

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P074

 

 

Undervoltage threshold

 

 

 

6 to 100

 

 

2

/

BR

 

 

4AHex

 

 

Response threshold for shutdown on line undervoltage. The

 

[%]

 

65

 

2

/

BR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

line supply voltage (P071) is the reference quantity.

 

 

 

 

 

 

 

 

 

 

 

 

 

Note:

P155: Maximum power failure time

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

 

PKW: 1HEX=1 %

PZD Gr.:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P077

 

 

FactSettingType

 

 

 

0 to 4

 

 

3

/U BR

 

*

 

 

Selective factory setting

 

 

 

 

 

0

 

3

/U

 

 

4DHex

 

 

This parameter can be changed in the "MLFB Input" state

 

 

 

 

 

 

 

 

 

 

 

 

 

(P052). If no MLFB has yet been entered, the selected factory

 

 

 

 

 

 

 

 

 

 

 

 

 

setting type becomes effective immediately an MLFB number

 

 

 

 

 

 

 

 

 

 

 

 

 

is entered and "MLFB Input" deselected (P052=0).

 

 

 

 

 

 

 

 

 

 

 

 

 

It is possible to activate a specific factory setting by selecting

 

 

 

 

 

 

 

 

 

 

 

 

 

"Par. Reset" (P052 = 1 or P970 = 0). This action does not,

 

 

 

 

 

 

 

 

 

 

 

 

 

however, change the setting in P077.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter values:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0: Current factory setting remains valid.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1: AFE with OP:

 

not currently implemented

 

 

 

 

 

 

 

 

 

 

 

 

 

2: AFE cabinet unit with terminal strip:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This setting initializes the following parameters to values

 

 

 

 

 

 

 

 

 

 

 

 

 

other than zero:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P554, P566, P603

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3: Current factory setting remains valid.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3: AFE cabinet unit with OP:

not currently implemented

 

 

 

 

 

 

 

 

 

 

 

 

 

Type:O2;

 

PKW: 1HEX=1

 

PZD Gr.: -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P078

 

 

Line frequency

 

 

 

 

50 to 60

 

 

2

/ ABR

 

 

4EHex

 

 

Frequency of incoming AC supply

 

 

 

[Hz]

 

50

 

2

/

A

 

 

 

 

Type=O2;

 

PKW: 1HEX=1 Hz

PZD Gr.:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P080

 

 

Line filter C/mF

 

 

 

 

0.000 to 10.000

 

 

3

/ BR

 

 

 

 

 

Capacitance of the filter capacitors of one phase of the AFE

 

 

 

0.000

 

3

/

BR

 

 

50Hex

 

 

line filter in mF for a "star circuit configuration". If the line filter

 

 

 

 

 

 

 

 

 

 

 

 

 

capacitors are connected in a “delta configuration”, then 300%

 

 

 

 

 

 

 

 

 

 

 

 

 

of the value must be parameterized.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

 

PKW: 1HEX=0.001

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12-6

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE