01.2004

Parameter List

 

 

12.5Closed-loop control

 

PNU

 

Parameter Name in OP1

 

 

Range

 

# of Indices

read:

_/_

 

 

 

 

 

 

 

[Unit]

 

Factory

write:

_/_

 

*:conf-P

 

Description

 

 

Value Texts

 

Settings

 

 

 

 

P120

 

CosPhi set

 

 

1.000 to 1.000

 

2

3 /

BR

 

 

 

 

Power factor cos(PHI) setpoint.

 

 

 

 

i001=1.000

3 /

BR

 

 

78Hex

 

Parameter values: 0.800 ... 1.000

inductive

 

 

 

i002=1.000

 

 

 

 

 

 

 

-0.800 ... -1.000 capacitive

 

 

 

 

 

 

 

 

 

 

RDS(2) parameter

 

 

 

 

 

 

 

 

 

 

 

Type=I2;

PKW: 1HEX=0.001 PZD Gr.: 4000HEX=4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P122

 

React. pow.(set)

 

 

140.0 to 140.0

 

2

3 /

BR

 

 

 

 

Reactive power setpoint for “reactive power compensation”

[%]

 

i001=0.0

3 /

BR

 

 

7AHex

 

mode (P164 = 0).

 

 

 

 

i002=0.0

 

 

 

 

 

 

Parameter values: Reactive power setpoint < 0 inductive

 

 

 

 

 

 

 

 

 

 

 

Reactive power setpoint > 0capacitive

 

 

 

 

 

 

 

 

 

 

RDS(2) parameter

 

 

 

 

 

 

 

 

 

 

 

Type=I2;

PKW: 1HEX=0.1 % PZD Gr.: 4000HEX = 400%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r123

 

Reactive power/kVAr

 

 

[kVAr]

 

3 /

BR

 

 

7BHex

 

Reactive power setpoint in kVAr calculated from P122 (for the

 

 

 

 

 

 

 

 

 

line supply voltage P071) for “reactive power compensation”

 

 

 

 

 

 

 

 

 

 

mode (P164 = 0)

 

 

 

 

 

 

 

 

 

 

 

Analog output: 100 % with code number (PWE) = 1638.4 kVA

 

 

 

 

 

 

 

 

 

 

Type=I2;

PKW: 1HEX=0.1 kVA

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P124

 

Sm.react.pow.

 

 

0 to 900

 

2

3 /

BR

 

 

 

 

Smoothing time constant for reactive power setpoint specified

 

[ms]

 

i001=50

3 /

BR

 

 

7CHex

 

in P122.

 

 

 

 

 

i002=50

 

 

 

 

 

 

RDS(2) parameter

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1 ms

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P125

 

Vd(set) factor

 

 

1.42 to 1.90

 

3 /

BR

 

 

 

 

Factor for the fixed setpoint of the DC link voltage. The line

 

 

 

1.58

3 /

BR

 

 

7DHex

 

supply voltage (P071) is the reference quantity.

 

 

 

 

 

 

 

 

 

 

Visualization parameters:

 

 

 

 

 

 

 

 

 

 

 

r126:

Vd fixed setpoint

 

 

 

 

 

 

 

 

 

 

 

r447:

Vd setpoint of setpoint node (P443)

 

 

 

 

 

 

 

 

 

 

r139:

Vd setpoint

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=0.01

PZD Gr.:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r126

 

Vd (set, par)

 

 

[V]

 

3 /

BR

 

 

 

 

Fixed setpoint for the DC link voltage setpoint V (calculated

 

 

 

 

 

 

 

7EHex

 

from P125)

 

 

 

 

 

 

 

 

 

 

 

 

Note:

Settable via P125 Vd(set) factor

 

 

 

 

 

 

 

 

 

 

Analog output: 100 % with code number (PWE) = 4 x P071

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1 V

PZD Gr.: 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P129

 

Vd reg. Kp

 

 

 

0.0 to 31.9

 

2

3 /

BR

 

 

 

 

Gain of DC-link voltage (Vd) controller

 

 

 

i001=2.0

3 /

BR

 

 

81Hex

 

RDS(2) parameter

 

 

 

 

i002=2.0

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=0.1

PZD Gr.: 0

 

 

 

 

 

 

 

 

P130

 

Vd reg. Kp dyn

 

 

0.0 to 31.9

 

2

3 /

BR

 

 

 

 

Dynamic gain of DC-link voltage (Vd) controller

 

 

 

i001=10.0

3 /

BR

 

 

82Hex

 

RDS(2) parameter

 

 

 

 

i002=10.0

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=0.1

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Siemens AG 6SE7087-6CX86-2BA1

12-9

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 79
Image 79
Siemens 400 V / 210...590 A operating instructions Closed-loop control