Siemens 400 V / 210...590 A operating instructions 12-21

Models: 400 V / 210...590 A

1 166
Download 166 pages 35.09 Kb
Page 91
Image 91

 

01.2004

 

 

 

 

 

 

 

Parameter List

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PNU

 

Parameter Name in OP1

 

Range

# of Indices

read:

_/_

 

 

 

 

 

 

 

 

[Unit]

Factory

write:

_/_

 

*:conf-P

 

Description

 

 

 

Value Texts

Settings

 

 

 

 

 

P589

 

Src No Ext Warn2

 

 

 

1 to 5001

2

3 /

BR

 

 

 

*

 

Source for control command "External alarm 2" (control word 2,

 

i001=1

3 /

BR

 

 

 

24DHex

 

bit 29)

 

 

 

 

 

i002=1

 

 

 

 

 

 

 

Parameter values: 0: Illegal setting

 

 

 

 

 

 

 

 

 

 

 

 

1:

No alarm

 

 

 

 

 

 

 

 

 

 

Other values:

See permissible settings in Section "Control

 

 

 

 

 

 

 

 

 

 

 

word"

 

 

 

 

 

 

 

 

 

 

B/R parameter

(process data connections of control word)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=L2; PKW: PKW format(HEX)=param. value

PZD Gr.: 0

 

 

 

 

 

 

 

P590

 

Src Base/Reserve

 

 

 

0 to 5001

3 /

BR

 

 

 

*

 

Source for basic / reserve setting switchover command (control

 

1005

3 /

BR

 

 

 

24EHex

 

word 2, bit 30)

 

 

 

 

 

 

 

 

 

 

 

 

Parameter values: 0:

Basic setting

 

 

 

 

 

 

 

 

 

 

 

 

1:

Reserve setting

 

 

 

 

 

 

 

 

 

 

 

 

1005: CUSA digital input 5

 

 

 

 

 

 

 

 

 

 

Other values:

See permissible settings in Section "Control

 

 

 

 

 

 

 

 

 

 

 

word"

 

 

 

 

 

 

 

 

 

 

 

 

(process data connections of control word)

 

 

 

 

 

 

 

 

 

Type=L2; PKW: PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

 

P600

 

Dst Ready for ON

 

 

 

0 to 5002

3

3 /

BR

 

 

 

*

 

Destination of the status bit 'Ready for ON' (status word 1, bit

 

i001=0

3 /

BR

 

 

 

258Hex

0)

 

 

 

 

 

i002=0

 

 

 

 

 

 

 

Power is ON, the drive can be switched on.

 

 

i003=0

 

 

 

 

 

 

 

Parameter values:

 

 

 

 

 

 

 

 

 

 

 

 

Depending on the selected index, all settings specified in

 

 

 

 

 

 

 

 

 

Section "Status word" (process data connections of status

 

 

 

 

 

 

 

 

 

word) may be parameterized.

 

 

 

 

 

 

 

 

 

 

Indices:

i001: GG:

 

Select a terminal on the basic unit

 

 

 

 

 

 

 

 

 

 

i002: SCI:

Select a terminal on SCI1/2

 

 

 

 

 

 

 

 

 

 

 

i003: TSY:

Select a terminal on TSY

 

 

 

 

 

 

 

 

 

 

Type=L2; PKW: PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P601

 

Dst Rdy for Oper

 

 

 

0 to 5002

3

3 /

BR

 

 

 

*

 

Destination of status bit "Ready to Run" (status word 1, bit 1)

 

i001=0

3 /

BR

 

 

 

259Hex

 

The DC link is charged, the pulses can be enabled.

 

 

i002=0

 

 

 

 

 

 

 

Parameter values, indices as for P600

 

 

i003=0

 

 

 

 

 

 

 

Type=L2; PKW: PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P602

 

Dst Operation

 

 

 

0 to 5002

3

2 /

BR

 

 

 

*

 

Destination of status bit "Run" (status word 1, bit 2)

 

 

i001=0

2 /

BR

 

 

 

25AHex

 

The device is running.

 

 

 

i002=0

 

 

 

 

 

 

 

Parameter values, indices as for P600

 

 

i003=0

 

 

 

 

 

 

 

Type=L2; PKW: PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P603

 

Dst Fault

 

 

 

 

0 to 5002

3

2 /

BR

 

 

 

*

 

Destination of status bit "Fault" (status word 1, bit 3)

 

i001=0

2 /

BR

 

 

 

25BHex

 

Note:

The active status (bit has H level) is output via the

 

i002=0

 

 

 

 

 

 

 

 

terminal in inverted form (broken-wire proof).

 

i003=0

 

 

 

 

 

 

 

Parameter values, indices as for P600

 

 

 

 

 

 

 

 

 

 

Type=L2; PKW: PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Siemens AG 6SE7087-6CX86-2BA1

12-21

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 91
Image 91
Siemens 400 V / 210...590 A operating instructions 12-21