Parameterization

01.2004

 

 

P052 = 5

P052 = 0

P

Select "Closed-loop control settings" (see Section "Closed-loop control settings")

Select "Return"

The operating display (r000) appears. At the same time, parameters and internal quantities are set to new values depending on the function selection.

The hardware is initialized.

If one of the fault messages F050/F070/F080 appears, see Section "Fault and alarm messages".

On completion of the selected function, operating display STARTING LOCKOUT (008) or READY FOR ON (009) appears.

11.2.6Closed-loop control settings (P052 = 5)

Function

This function is used to alter the closed-loop control settings (AFE

 

data).

Condition

The "Closed-loop control settings" can be made in the FAULT (007),

 

STARTING LOCKOUT (008) or READY FOR ON (009).

Result

All parameters which can be written in the "Closed-loop control

 

settings" state ("A", see right-hand column in Parameter List) can be

 

altered by this function.

 

"Closed-loop control settings" is terminated by resetting the status

 

(P052 = 0) with calculation of internal quantities.

P052 = 5

Select "Closed-loop control settings"

P051 = 3

P052 = 0

Access level "Expert Mode"

(in case parameters which require Export Mode need to be altered)

Change selected parameters which can be altered in the "Closed-loop control settings" state.

Select "Return"

P

The operating display (r000) appears. At the same time, parameters and internal quantities are set to new values depending on the function selection.

On completion of the selected function, operating display STARTING LOCKOUT (008) or READY FOR ON (009) appears.

11-10

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE