Parameter List

01.2004

 

 

PNU

 

Parameter Name in OP1

 

Range

 

# of Indices

 

read:

_/_

 

 

 

 

 

 

[Unit]

 

Factory

 

write:

_/_

*:conf-P

 

Description

 

Value Texts

 

Settings

 

 

 

 

P131

 

Vd regulator Ti

 

0.5 to 100.0

2

3 /

BR

 

 

 

Integration time constant of the DC-link voltage (Vd) controller [ms]

 

i001=20.0

3 /

BR

 

83Hex

 

RDS(2) parameter

 

 

 

i002=20.0

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=0.1 ms

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r139

 

Ud (set)

 

 

 

 

 

3 /

BR

 

8BHex

 

Setpoint of DC-link voltage in V

 

[V]

 

 

 

 

 

 

 

Note:

 

The Vd setpoint (r139) can be higher than the set

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vd setpoint (r447). For a high line supply voltage

 

 

 

 

 

 

 

 

 

 

and/or a high capacitive reactive current, the DC

 

 

 

 

 

 

 

 

 

 

link voltage is automatically increased so that a

 

 

 

 

 

 

 

 

 

 

minimum modulation reserve is maintained.

 

 

 

 

 

 

 

 

Analog output: 100 % with code number (PWE) = 4 x P071

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1 V

PZD Gr.: 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r150

 

Control status

 

 

 

3 /

BR

 

 

 

Status word of the closed-loop control

 

 

 

 

 

 

 

 

96Hex

 

Parameter values:

 

 

 

 

 

 

 

 

 

 

Bit00 = 1:

Initialization of closed-loop control complete

 

 

 

 

 

 

 

 

Bit01 = 1:

Ext. 24V power supply faulted

 

 

 

 

 

 

 

 

Bit02 =

 

Reserved

 

 

 

 

 

 

 

 

 

 

Bit03 = 1:

Precharging completed

 

 

 

 

 

 

 

 

 

 

Bit04 = 1:

Active current >= 0 (motoring, rectifier operation)

 

 

 

 

 

 

 

 

Bit05 = 1:

Reactive current >= 0 (capacitive)

 

 

 

 

 

 

 

 

Bit06 = 1:

Active current at limit

 

 

 

 

 

 

 

 

 

 

Bit07 = 1:

Reactive current at limit

 

 

 

 

 

 

 

 

 

 

Bit08 = 1:

Absolute current value at limit (r174)

 

 

 

 

 

 

 

 

Bit09 = 1:

Smoothed line supply voltage < 80 % of P071

 

 

 

 

 

 

 

 

Bit10 = 1:

Smoothed line supply voltage > 105 or 110 % of

 

 

 

 

 

 

 

 

 

 

P071

 

 

 

 

 

 

 

 

 

 

Bit11 = 1:

Control factor at limit

 

 

 

 

 

 

 

 

 

 

Bit12 = 1

Ud2t integrator increasing

 

 

 

 

 

 

 

 

 

 

Bit13 =

1

DC link voltage < 90% of setpoint

 

 

 

 

 

 

 

 

Bit14 =

1

DC link voltage > 110% of setpoint

 

 

 

 

 

 

 

 

Bit15 =

1

Smoothed line supply voltage < P074

 

 

 

 

 

 

Coding of bits on the PMU:

151413121110 9 87 65 4 3 21 0

 

Type=V2; PKW: 1HEX=1

PZD Gr.: 0

 

r152

Active RDS

2 / ABR

98Hex

Active reserve data set of the AFE

 

 

Analog output: 100 % with code number (PWE) = 16384

 

 

Type=O2; PKW: 1HEX=1

PZD Gr.: 0

 

12-10

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 80
Image 80
Siemens 400 V / 210...590 A operating instructions 12-10, R139, R150 Control status, R152 Active RDS