Connecting-Up and Wiring

 

 

7.2.2Auxiliary power supply, precharging

X9 - external DC 24 V supply, precharging contactor control

5

4

3

2 1

The 5-pole terminal strip is used for connecting up a 24 V voltage supply and for connecting a precharging contactor.

The connections for the contactor control are floating.

The position of the terminal strip can be seen from the connection overviews.

Terminal

Designation

Meaning

Range

5

Precharge contr.

Precharging contactor control

AC 230 V

4

Precharge contr.

Precharging contactor control

1 kVA

3

n.c.

Not connected

 

2

0 V

Reference potential

0 V

1

+24 V (in)

24 V voltage supply

DC24 V 3.5 A

Connectable cross-section: 2.5 mm2 (AWG 12)

Table 7-4 Connection of external DC 24 V aux. voltage supply and precharging contactor control

Fan supply

AFE inverters of construction type J (compare above) require a supply

 

cable cross-section of 2.5 mm2 (AWG 12). Connection to

 

F101 and F102 (fan fuses).

7.2.3Protective conductor connection

 

For AFE basic mains module, directly via the mounting surface and via

 

PE screw.

 

For AFE inverter via PE1 and PE2 and contact via the mounting

 

surface.

NOTE

 

It is important to ensure that the basic mains module and the AFE

 

inverter are earthed at the same potential, use equipotential bonding if

 

necessary.