Connecting-Up and Wiring

01.2004

 

 

7.3Control terminals

7.3.1Standard connections of the AFE inverter

 

The basic version of the converter features the following control

 

 

terminals on the CUSA board:

 

 

 

 

 

 

 

 

Control terminal strips X100, X101 and X102 on CUSA electronics

 

 

 

board

 

 

 

 

 

 

 

 

 

 

 

Connection for OP1S operator control panel

 

 

 

 

 

One serial interface (USS bus, RS485)

 

 

 

 

 

 

Serial interfaces RS485 and RS232 (SCom1) on PMU X300

 

CAUTION

 

 

 

 

 

The CUSA board contains components which can be destroyed by

 

 

electrostatic discharge. These components can be very easily

 

 

destroyed if not handled with caution.

 

 

 

 

 

 

 

See also ESD precautions outlined in Section "Definitions and

 

 

warnings".

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connectors for

The connectors for the control terminal strip are included in the scope

 

control terminal

of supply and ready connected to the cable harness of the AFE basic

 

strip

mains module (cf. Fig. 7-1).

 

 

 

 

 

 

 

 

 

Cables with cross-sections from 0.14 mm2 to 1.5 mm2 (AWG: 26 to

 

 

16), or 1 mm2 (AWG: 18) can be connected using stranded wire with

 

 

lugs to the connectors (recommended: 0.5 mm2 (AWG: 20)). The

 

 

connectors can be identified by the pin numbers (Table 7-5), connector

 

 

positions on the board are shown in Fig. 7-8.

 

 

 

 

 

Two screen clamps and four cable ties are required from the loose

 

 

components supplied to connect the control cables.

 

 

 

 

Connector X9 is needed to control the pre-charging operation and to

 

 

connect an external power supply (see Fig. 7-8).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connector

 

Label

 

 

 

 

 

 

 

 

X100

eight-pin, coded

 

1

2

3

CU

6

7

8

 

 

 

X101

eight-pin, coded

 

13

14

15

CU

18

19

20

 

 

 

X102

ten-pin

 

25

26

27

28

CU

31

32 33 34

 

Table 7-5