Basic Function Check

01.2004

 

 

Enabling control After successful precharging and actual value check

P561 = 1

Reaction: The AFE inverter pulse is audibly and evenly

 

The DC link voltage (r006) goes to the value P071 x

 

P125, and is stable with slight fluctuations ± approx.

 

1 %.

 

The current consumption of the AFE inverter (r004)

 

should be no greater than 20% of the rated current of

 

the unit (cf. P072).

Fault:

Replace CUSA or VSB in the event of clear deviations

 

in the current consumption.

The basic function check of the AFE rectifier/regenerative feedback unit has been completed and the unit is operable.

Commissioning can now take place depending on project planning.