Parameter List

 

 

 

 

01.2004

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PNU

Parameter Name in OP1

 

Range

# of Indices

 

read:

_/_

 

 

 

 

 

[Unit]

Factory

 

write:

_/_

 

*:conf-P

Description

 

 

Value Texts

Settings

 

 

 

 

 

 

P517

SetActValDev.Ud

 

0.00 to 100.00

2

 

3 /

BR

 

 

 

 

Setpoint/actual value deviation in DC-link voltage Vd

[%]

i001=2.00

 

3 /

B

 

 

 

205Hex

In the case of a large deviation between Vd setpoint and

 

i002=2.00

 

 

 

 

 

 

 

actual value, message "Setpoint actual value deviation" (status

 

 

 

 

 

 

 

 

 

word 1, bits 8 (r552) is activated.

 

 

 

 

 

 

 

 

 

 

Cf. P518 Minimum time of setpoint/actual value deviation

 

 

 

 

 

 

 

 

 

Ref. quantity: Vd(set) (r126)

 

 

 

 

 

 

 

 

 

 

RDS(2) parameter

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=0.01 %

PZD Gr.: 0

 

 

 

 

 

 

 

 

P518

Deviation Time

 

0.0 to 10.00

2

 

3 /

BR

 

 

 

 

Minimum time for setpoint/actual value deviation

[s]

i001=0.10

 

3 /

B

 

 

 

206Hex

When there is a deviation between the setpoint/actual value

 

i002=0.10

 

 

 

 

 

 

 

(P517), the message "Setpoint/actual value deviation" (status

 

 

 

 

 

 

 

 

 

word 1 bit 8 (r552)) is output when the time in P518 runs out.

 

 

 

 

 

 

 

 

 

RDS(2) parameter

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=0.01 s

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 