Parameter List

 

 

 

 

01.2004

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PNU

Parameter Name in OP1

 

Range

# of Indices

 

read:

_/_

 

 

 

 

 

[Unit]

Factory

 

write:

_/_

 

*:conf-P

Description

 

Value Texts

Settings

 

 

 

 

 

 

P604

Dst NO OFF2

 

0 to 5002

3

 

3 /

BR

 

 

 

*

Destination of the status bit 'No OFF2 command' (status word

 

i001=0

 

3 /

BR

 

 

 

25CHex

1, bit 4)

 

 

 

i002=0

 

 

 

 

 

 

 

Parameter values, indices as for P600

 

 

i003=0

 

 

 

 

 

 

 

Type=L2; PKW: PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P606

Dst ON blocked

 

0 to 5002

3

 

3 /

BR

 

 

 

*

Destination of the status bit "Starting lockout active" (status

 

i001=0

 

3 /

BR

 

 

 

25EHex

word 1, bit 6)

 

 

i002=0

 

 

 

 

 

 

 

Note:

The active status (bit has H level) is output via the

 

i003=0

 

 

 

 

 

 

 

 

terminal in inverted form (broken-wire proof).

 

 

 

 

 

 

 

 

 

Parameter values, indices as for P600

 

 

 

 

 

 

 

 

 

 

Type=L2; PKW: PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P607

Dst Warning

 

0 to 5002

3

 

2 /

BR

 

 

 

*

Destination of the status bit "Alarm" (status word 1, bit 7)

 

i001=0

 

2 /

BR

 

 

 

25FHex

Note:

The active status (bit has H level) is output via the

 

i002=0

 

 

 

 

 

 

 

 

terminal in inverted form (broken-wire proof).

 

i003=0

 

 

 

 

 

 

 

Parameter values, indices as for P600

 

 

 

 

 

 

 

 

 

 

Type=L2; PKW: PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P608

Trg Bit Deviat.

 

0 to 5002

3

 

3 /

BR

 

 

 

*

Destination of the status bit "DC-link voltage setpoint = Actual

 

i001=0

 

3 /

BR

 

 

 

260Hex

DC-link voltage' (status word 1, bit 8) - cf. P517; see Section

 

i002=0

 

 

 

 

 

 

 

"Status word" for details

 

 

i003=0

 

 

 

 

 

 

 

Parameter values, indices as for P600

 

 

 

 

 

 

 

 

 

 

Type=L2; PKW: PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

 

 

P611

Dst Low Voltage

 

0 to 5002

3

 

3 /

BR

 

 

 

*

Destination of the status bit "Low voltage' (status word 1, bit 11)

 

i001=0

 

3 /

BR

 

 

 

263Hex

Note:

The active status (bit has H level) is output via the

 

i002=0

 

 

 

 

 

 

 

 

terminal in inverted form (broken-wire proof).

 

i003=0

 

 

 

 

 

 

 

Parameter values, indices as for P600

 

 

 

 

 

 

 

 

 

 

Type=L2; PKW: PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

 

 

P612

Dst Contactor

 

0 to 5002

3

 

3 /

BR

 

 

 

*

Destination of the status bit "Energize main contactor'

 

i001=1002

 

3 /

BR

 

 

 

264Hex

(status word 1, bit 12); H level: Energize contactor!

 

 

i002=0

 

 

 

 

 

 

 

CAUTION:

For safety reasons, this status bit is always

 

i003=0

 

 

 

 

 

 

 

 

connected to digital output 2 on the CUSA board

 

 

 

 

 

 

 

 

 

 

on the AFE. It is not possible or permissible to

 

 

 

 

 

 

 

 

 

 

connect the bit in any other way as it protects the

 

 

 

 

 

 

 

 

 

 

AFE against damage by preventing the main

 

 

 

 

 

 

 

 

 

 

contactor from closing before the DC link has

 

 

 

 

 

 

 

 

 

 

been charged.

 

 

 

 

 

 

 

 

 

 

Type=L2; PKW: PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

 

 

P614

Dst.Gen.Mot.

 

0 to 5002

3

 

3 /

BR

 

 

 

*

Destination of the status bit "Generator/motor operation" (status

 

i001=0

 

3 /

BR

 

 

 

266Hex

word 1, bit 14)

 

 

i002=0

 

 

 

 

 

 

 

Meaning:

L: Motor-mode operation (rectifier)

 

 

i003=0

 

 

 

 

 

 

 

 

H: Generator-mode operation (regen. feedback)

 

 

 

 

 

 

 

 

 

Parameter values, indices as for P600

 

 

 

 

 

 

 

 

 

 

Type=L2; PKW: PKW format(HEX)=param.value