Siemens 400 V / 210...590 A AFE inverter construction type G, Door/roof openings, Partitions

Models: 400 V / 210...590 A

1 166
Download 166 pages 35.09 Kb
Page 22
Image 22

Installation

01.2004

 

 

5.2.3AFE inverter (construction type G)

Mounting surface

H

h

 

c

b

a

350

a

 

B

 

 

 

 

Side view

 

Front view

 

Cutouts for

M8 screw

Dimen-

sions Type

[mm]G

a119

b270

c25

B508

H 1450

h 1375

Fig. 5-4 Mounting dimension, construction type G

Partition measures

Door/roof openings

 

An underpressure is created in the openings of the cabinet doors due to

 

the flow of air. This is dependent on the volumetric flow and the

 

hydraulic cross-section of the openings.

 

The flow causes a build-up (over) pressure in the roof or in the top

 

cover.

 

As a result of the difference in pressure between the overpressure at

 

the top and the underpressure at the bottom of the cabinet, a flow of air

 

is created inside the unit, a so-called arcing short-circuit. This can be

 

stronger or weaker depending on the volumetric flow and the door/roof

 

opening cross-section.

 

As a result of the flow inside the unit, air which is already pre-heated

 

enters the heat sinks which causes an excessively high component

 

temperature rise. In addition, a different, more unfavourable operating

 

point is set for the fan.

 

If the units are operated with an arcing short-circuit, this will result in the

 

failure of the units or in their destruction!

 

An arcing short-circuit must be prevented by the provision of

 

partitions.

 

The switch cabinets adjacent to the inverter cabinets must also be

 

taken into consideration in this case.

5-4

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE