Control and Status Words

01.2004

 

 

Bit 13: Reserved

Bit 14: "Motor operation" signal (L)

LOW signal

AFE operates in rectifier mode (active current >= 0)

 

 

Bit 15: Reserved

 

 

 

Bit 16: Reserved

 

 

 

Bit 17: Reserved

 

Bit 18: "Current limit active" signal (L)

LOW signal

AFE operates at the present current limit setting

Meaning

If the AFE output current is limited, the DC-link voltage can no

 

longer be regulated to the selected setpoint.

 

Output at terminal strip (CUSA, SCB1) with L signal.

Bit 19: "External fault 1" signal (H)

HIGH signal

" External fault 1"

Meaning

An "External fault 1" is active in control word bit 1.

 

Output at terminal strip (CUSA, SCB1) with L signal.

Bit 20: "External fault 2" signal (H)

HIGH signal

" External fault 2"

Meaning

An "External fault 2" is active in control word bit 26.

 

Output at terminal strip (CUSA, SCB1) with L signal.

Bit 21: "External alarm" signal (H)

HIGH signal

"External alarm"

Meaning

An "External alarm 1" is active in control word bit 28 or an "External

 

alarm 2" in control word bit 29.

 

Output at terminal strip (CUSA, SCB1) with L signal.

Bit 22: "AFE i2t alarm" signal (H)

HIGH signal Meaning

"AFE i2t alarm" (A025)

If the converter continues to operate under the current load conditions, the AFE will be thermally overloaded.

Output at terminal strip (CUSA, SCB1) with L signal.

13-20

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 130
Image 130
Siemens 400 V / 210...590 A Bit 19 External fault 1 signal H High signal, Bit 20 External fault 2 signal H High signal