Siemens 400 V / 210...590 A 12-28, P686 SCom/SCB # PrDat, P687 SCom/SCB TlgOFF

Models: 400 V / 210...590 A

1 166
Download 166 pages 35.09 Kb
Page 98
Image 98

 

 

Parameter List

 

 

 

 

 

 

 

 

 

 

01.2004

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PNU

 

 

Parameter Name in OP1

 

 

 

Range

 

 

# of Indices

 

read:

_/_

 

 

 

 

 

 

 

 

 

 

 

 

[Unit]

 

 

Factory

 

write:

_/_

 

 

*:conf-P

 

 

Description

 

 

 

 

 

Value Texts

 

 

Settings

 

 

 

 

 

 

 

P685

 

 

SCom/SCB PCV

 

 

 

 

 

0 to 127

 

2

 

3 /

BR

 

 

 

*

 

 

Number of words (16-bit) in PKW section in the net data block of

 

 

 

 

 

i001=127

 

3 /

BR

 

 

 

 

2ADHex

 

 

the telegram (see Section "Serial interfaces")

 

 

 

 

 

i002=127

 

 

 

 

 

 

 

 

 

 

Parameter values: 0:

No PKW section

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3, 4: PKW section is 3 (ident.,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ind,value), 4 words long

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

127: Variable PKW length for transmission

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of parameter description and texts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indices: i001 = SST1: Serial interface 1 (CUSA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i002 =

SCB:

SCB if P682 = 1, 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1.0

PZD Gr.: -

 

 

 

 

 

 

 

 

 

 

 

 

 

P686

 

 

SCom/SCB # PrDat

 

 

 

 

0 to 16

 

2

 

3 /

BR

 

 

 

*

 

 

Number of words (16-bit) of process data section in the net data

 

 

 

 

 

i001=2

 

3 /

BR

 

 

 

 

 

block of the telegram (see Section "Serial interfaces").

 

 

 

 

 

 

 

 

 

 

2AEHex

 

 

 

 

 

 

 

i002=2

 

 

 

 

 

 

 

 

 

Indices:

i001 =

SST1: Serial interface 1 (CUSA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i002 =

SCB:

SCB if P682 = 1, 2, 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1.0

PZD Gr.: -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P687

 

 

SCom/SCB TlgOFF

 

 

 

 

0 to 6500

 

2

 

3 /

BR

 

 

 

*

 

 

Telegram failure time for CUSA and SCB

 

 

[ms]

 

 

i001=0

 

3 /

BR

 

 

 

 

 

Shutdown on faults occurs if no correct telegram is received

 

 

 

 

 

 

 

 

 

2AFHex

 

 

 

 

 

 

 

i002=0

 

 

 

 

 

 

 

 

 

within the specified time.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting instructions:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value 0: No monitoring and no fault shutdown; parameterize

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for sporadic (acyclic) telegrams (e.g. OP on SST1).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If a TB is installed in slot 2 and an SCB in slot 3, then the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting in i002 is irrelevant.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indices: i001 = SST1: Serial interface 1 (CUSA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i002 =

SCB:

SCB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1.0 ms

PZD: 4000HEX=1638.4 ms

 

 

 

 

 

 

 

 

 

 

 

 

 

P689

 

 

SCB Peer2PeerExt

 

 

 

 

0 to 1

 

5

 

3 /

BR

 

 

 

 

 

 

 

Direct transfer of peer-to-peer receive data of the SCB.

 

 

 

 

 

i001=0

 

3 /

BR

 

 

 

 

2B1Hex

 

 

Identification of words in received peer-to-peer telegram which

 

 

 

 

 

i002=0

 

 

 

 

 

 

 

 

 

 

must be transferred on directly.

 

 

 

 

 

 

i003=0

 

 

 

 

 

 

 

 

 

 

Param. values:

0: No immediate transfer (to CUSA only)

 

 

 

 

 

i004=0

 

 

 

 

 

 

 

 

 

 

 

 

1: Direct transfer (incl. transfer to CUSA)

 

 

 

 

 

i005=0

 

 

 

 

 

 

 

 

 

 

Indices: i001 =

W01:

Word 01 of (process data section

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of telegram)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i002 =

W02:

Word 02 of (process data section

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

...

 

of telegram)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i005 =

W05:

Word 05 of (process data section

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of telegram)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Precondition: P682 = 3 (peer-to-peer protocol)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1.0

PZD Gr.: -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12-28

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 98
Image 98
Siemens 400 V / 210...590 A 12-28, P686 SCom/SCB # PrDat, P687 SCom/SCB TlgOFF, P689 SCB Peer2PeerExt