514067-UAD-A-0509

TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)

 

BACnet

BACnet

 

 

 

 

 

Read/

Object

Object

 

 

 

 

 

Write

Type

Inst

Descriptor

Default

Min

Max

Point Description

R

(5) BV

14

LOW_SUP_VOLT

Low Supply Voltage (0=comps not overrid-

 

 

 

 

 

 

 

den by LSV, 1=comps overridden)

R/W

(5) BV

96

MANUAL_WRITE

Manual Write Command to ModlINC

R/W

(2) AV

28

MAX_TH_OFSET

3

0

5

Max Temperature/Humidity Setpoint Offset

R/W

(2) AV

30

MAX_DMV_ECON

50

0

100

Maximum Demand Ventillation Economizer

 

 

 

 

 

 

 

Position

R

(5) BV

11

MODBUS_ALARM

Modbus Communication Alarm

R

(5) BV

9

MOD_EX_INST

Modulating Exhaust Installed

R/W

(2) AV

61

MWU_RAT_STPT

70

50

85

Morning Warm-Up and VAV Heating: Return

 

 

 

 

 

 

 

Air Temperature Setpoint (degrees F)

R

(5) BV

6

MORN_WARM-UP

Morning Warm-Up Enabled

R

(2) AV

16

NUMBER_COMPS

Number of Compressors Available

R

(2) AV

48

NUMBER_HEAT

Number of Heat Stages Available

R/W

(2) AV

1

OCC_COOL_SP

72

45

99

Occupied Cooling Setpoint

R/W

(5) BV

1

OCCUPIED_ENA

Occupied Enabled

R/W

(2) AV

50

OCC_HEAT_SP

68

45

99

Occupied Heating Setpoint

R

(5) BV

93

OCC_COMS_ENA

Occupied Thermostat or Communication

 

 

 

 

 

 

 

Input Enabled

R

(2) AV

17

OP_COOL_STPT

Operating Cooling Setpoint

R

(2) AV

49

OP_HEAT_STPT

68

45

99

Operating Heating Setpoint

R/W

(2) AV

69

OP_STPT_DIF

1

1

5

Operating Setpoint Differential

R/W

(2) AV

74

OAT_COOL_L_O

45

0

100

Outdoor Air Temperature Cooling Lockout

 

 

 

 

 

 

 

Temperature

R/W

(2) AV

54

OAT_HEAT_L_O

75

0

100

Outdoor Air Temperature HeatingLockout

 

 

 

 

 

 

 

Temperature

R

(2) AV

11

AMB_AIR_ENTH

Outside Air Enthalpy

R

(2) AV

10

AMB_AIR_HUM

Outside Air Humidity

R

(5) BV

37

OAH_SENSOR

Outside Air Humidity Sensor Enabled

R

(2) AV

7

AMB_TEMP

Outside Air Temperature

R

(2) AV

9

OAQ_VALUE

1000

0

5000

Outside Demand Ventilation (OAQ) Value

 

 

 

 

 

 

 

(PPM)

R

(5) BV

8

PWR_EX_INST

Power Exhaust Installed

R

(5) BV

20

POP_ENABLED

Pre-Occupancy Purge Enabled

R/W

(2) AV

81

POP_HOURS

4

0

23

Pre-Occupancy Purge Time (hours)

R/W

(2) AV

82

POP_MINUTES

0

0

59

Pre-Occupancy Purge Time (minutes)

R

(5) BV

17

PURGE_SWITCH

Purge Switch Status (0=open,1=closed)

R/W

(5) BV

12

REDLINE

Redline (0=clear redline, 1=set redline

 

 

 

 

 

 

 

operation)

R

(5) BV

4

REM_CONT_ENA

Remote Control Enabled

R

(2) AV

13

RET_AIR_ENTH

Return Air Enthalpy

R

(2) AV

12

RET_AIR_HUM

Return Air Humidity

R

(2) AV

5

RET_AIR_TEMP

Return Air Temperature

R

(5) BV

38

RAH_SENSOR

Return/Inside Air Humidity Sensor Enabled

R

(2) AV

6

SPACE_TEMP

Space (Indoor) Air Temperature

8

Johnson Controls Unitary Products

Page 8
Image 8
Simplicity 514067-UAD-A-0509 manual Lowsupvolt