TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)

 

BACnet

BACnet

 

 

 

 

 

Read/

Object

Object

 

 

 

 

 

Write

Type

Inst

Descriptor

Default

Min

Max

Point Description

R/W

(2) AV

69

OP_STPT_DIF

1

1

5

Operating Setpoint Differential

R/W

(2) AV

70

SAT_ALM_COOL

0

0

80

Supply Air Temperature Alarm Setpoint for

 

 

 

 

 

 

 

Cooling

R/W

(2) AV

71

SPCE_ALM_TMP

0

0

25

Space Sensor Alarm Temperature

 

 

 

 

 

 

 

(degrees F, 0 = disabled)

R/W

(2) AV

72

SPCE_ALM_TIM

0

0

120

Space Sensor Alarm Time (minutes F,

 

 

 

 

 

 

 

0 = disabled)

R/W

(2) AV

73

SP_OFF_RANGE

3

0

5

Space Temprature Sensor Offset Range

 

 

 

 

 

 

 

(0-5 degrees)

R/W

(2) AV

74

OAT_COOL_L_O

45

0

100

Outdoor Air Temperature Cooling Lockout

 

 

 

 

 

 

 

Temperature

R/W

(2) AV

75

UNOC_OVR_TP

60

0

240

Unoccupied Override Time Period

R

(2) AV

76

H1_ACCUM_HRS

Heating #1 Accumulated Run Time (in hours)

R

(2) AV

77

H2_ACCUM_HRS

Heating #2 Accumulated Run Time (in hours)

R

(2) AV

78

H3_ACCUM_HRS

Heating #3 Accumulated Run Time (in hours)

R/W

(2) AV

79

OAQ_STPT

1000

0

5000

Air Quality Setpoint Outside

R/W

(2) AV

80

IO_DVNT_STPT

700

0

2000

Indoor/Outdoor Demand Ventilation Setpoint

R/W

(2) AV

81

POP_HOURS

4

0

23

Pre-Occupancy Purge Time (hours)

R/W

(2) AV

82

POP_MINUTES

0

0

59

Pre-Occupancy Purge Time (minutes)

R/W

(2) AV

84

ECON_RAEN_SP

27

10

50

Economizer Return Air Enthalpy Setpoint

R/W

(5) BV

1

OCCUPIED_ENA

Occupied Enabled

R

(5) BV

2

HYDRONC_HEAT

Hydronic Heat Enabled

R

(5) BV

3

HH_REVER_VLV

Hydronic Heat Reverse Actuated Valve

 

 

 

 

 

 

 

Installed

R

(5) BV

4

REM_CONT_ENA

Remote Control Enabled

R

(5) BV

5

VAV_OCC_HEAT

VAV Occupied Heating Enabled

R

(5) BV

6

MORN_WARM-UP

Morning Warm-Up Enabled

R

(5) BV

7

ECONO_INST

Economizer Installed

R

(5) BV

8

PWR_EX_INST

Power Exhaust Installed

R

(5) BV

9

MOD_EX_INST

Modulating Exhaust Installed

R

(5) BV

10

EX_VFD_INST

Exhaust VFD Installed

R

(5) BV

11

MODBUS_ALARM

Modbus Communication Alarm

R/W

(5) BV

12

REDLINE

Redline (0=clear redline, 1=set redline

 

 

 

 

 

 

 

operation)

R/W

(5) BV

13

LOADSHED

Loadshed (0=clear loadshed, 1=set loadshed

 

 

 

 

 

 

 

operation)

R

(5) BV

14

LOW_SUP_VOLT

Low Supply Voltage (0=comps not

 

 

 

 

 

 

 

overridden by LSV, 1=comps overridden)

R

(5) BV

15

DIRT_FILT_SW

Dirty Filter Switch Status (0=open,1=closed/

 

 

 

 

 

 

 

fault)

R

(5) BV

16

AIR_PROOF_SW

Air Proving Switch Status (1=closed,

 

 

 

 

 

 

 

0=open/no air flow)

R

(5) BV

17

PURGE_SWITCH

Purge Switch Status (0=open,1=closed)

R

(5) BV

18

HGR_STAT

Hot Gas Reheat Output Status (0=output is

 

 

 

 

 

 

 

OFF, 1=output is ON)

12