Input Block Model Indication Method

Input Block

Model indication method

EX250 IE

Block type

1

Input points : 2, M12 connector (2pcs.)

2

Input points : 4,

M12 connector (2pcs.)

3

Input points : 4,

M8 connector (4pcs.)

Part Names

EX250-IE1

EX250-IE2

EX250-IE3

Tie-rod (2 pcs.)

Accessory

No.

Part names

Application

1

Input equipment connector

Connects the input equipment such as sensor, etc. Note1

 

 

 

2

Operation display LED

Displays the power source and input status. Note2

 

 

 

Note1 : For wiring method, refer to subsection "Wiring" (page 20) of section "Input Block" in this manual.

Note2 : For display and setting, refer to "Display/Setting" (page 22) in section "Input Block" in this manual.

Dimensions ( unit : mm )

EX250-IE1/2

 

EX250-IE3

 

21

21

 

 

 

 

 

 

 

 

 

 

72.6

67.4

59.8

59.8

Mounting/Installation

Refer to subsection "Mounting/Installation" (page 7) in this manual.

Specifications

Applicable sensor

Current source type(PNP input)

Current sink type(NPN input) *Selected with a switch.

 

 

 

 

Rated voltage

24VDC (It can have a voltage drop for 1V at max. to the

power source voltage of the SI Unit.)

 

 

 

 

Logical "1" input voltage VH

11 to 30V

Logical "0" input voltage VL

-3 to +5V

Logical "1" input current IH

8mA Typ.

Connection of 2-wire sensor

Possible

Logical "1" input current IL

Max.2.5mA

Input delay time

3msec. Typ.

Supply current to sensor

Max. 120mA / Input Block

Connector type of the input

IE1/2

M12 connector (4 pin, plug or 5 pin, plug)

equipment

 

 

IE3

M8 connector (3 pin, plug)

 

 

 