Southbend STRE-3D owner manual Steamer Not Heating Up, Power Light Is Not Lit

Models: STRE-3D

1 48
Download 48 pages 50.24 Kb
Page 22
Image 22

SERVICE

STRATOSTEAM COUNTERTOP STEAMER

Figure 11

Steamer Not Heating Up, “Power” Light Is Not Lit

Steamer not heating up, “Power” light not lit.

DISCONNECT POWER AT CIRCUIT BREAKER

Remove right side panel for access.

Reconnect power at circuit breaker.

Turn lever to “ON” position and close door (to actuate door switch).

Check voltage between terminals L1 and L3 on contactor

(see page 27).

 

Is measured

 

No

Yes

voltage 208, 220, or 240

 

volts?

 

 

 

DISCONNECT POWER AT CIRCUIT BREAKER

Check resistance between heating-cartridge contactor terminals

as described on page 25.

Test operation of power switch (see page 26). Replace if

necessary. If power switch is OK, replace “Power” light and follow

procedure on page 23.

 

Is measured resistance

 

No

Yes

in the range specified on

 

page 25?

 

Disconnect all the heating

cartridges from the contactor. Measure the resistance across the leads each cartridge. Replace any cartridge that shows either an open or short circuit.

Check main fuses (480V

models only) and replace as

needed.

PAGE 22 OF 48

OWNERS MANUAL 1185184

Page 22
Image 22