The following table lists 6017 TCU pipe sizes.

Connections for TO PROCESS and FROM PROCESS lines are:

2" NPT (50.8 mm) at 90 gpm (341 lpm)

2-1/2" NPT (63.5 mm) at 150 gpm (568 lpm)

3" NPT (76.2 mm) at 200 gpm (757 lpm)

Water connections for COOLING WATER SUPPLY and

COOLING WATER DRAIN are:

¾” NPT (19.1 mm) for 3.9 & 6.7 sq. ft. heat exchangers.

1" NPT (25.4 mm) for 13, 21, & 27 sq. ft. heat exchangers.

The customer is responsible for conversions to metric standards.

Notes: Always use a backup wrench to support 6017 unit piping when making connections. Make sure all external piping is supported independently of the 6017 unit.

Sterling, Inc. recommends that you have strainers installed on the cooling water inlets and customer-supplied shut-off valves on all piping connections. Use common black welded pipe for permanent installations.

The 6017 is designed to operate with an open, unrestricted drain line. Steam rapidly expands within the heat exchanger, so any overpressure condition from backpressure or standing columns of water against the drain must be avoided.

If you must use a pipe joint compound, use a compound that can withstand the high temperatures and pressures of your 6017 unit. Always insulate all piping to prevent burn hazards and to retain heat. Make sure insulation is properly rated for maximum operating temperatures of your 6017 unit.

Piping Considerations for Mobile Installations

Because your 6017 unit is not fitted with casters, it should be secured to the floor with the appropriate hardware. You can purchase high-quality flexible metal hose from Sterling/Sterlco to allow for thermal expansion of the process piping; state the length you want when ordering.

6017 Series Hot Oil Large Temperature Control Units