4-6 Setting the Redundant Safety Controller

The Redundant Safety Controller alarm setting is changed by pressing the up and down keys to input the alarm value. The upper display reading indicates the Process Value, while the lower display indicates the High Point Setting alarm value. The factory setting for the High Point Alarm Value is 150°F (-23°C).

Always put your set point to 30°F above set point.

To set the redundant safety controller:

1.Press the P button.

2.The controller will ask for a password. Press the Up button until you get to 10.

3.Press the Up button until you get to your desired temperature.

4.Press P again until you get to Run.