INSTALLATION INSTRUCTIONS
SITE REQUIREMENTS
5.2When the appliance is installed in a masonry chimney without a liner, there must be a minimum debris collection area, Diagram 1b
1b
AR2006
5.3DO NOT install onto a combustible wall; all combustible materials must be removed from the area shown in Diagram 1c.
1c
440 400
1160
not to scale
840
100960
AR1226
5.4A combustible shelf must be a minimum of 400mm above the top of the appliance. This is based on a 150mm deep shelf. For every extra 13mm of depth add 25mm above the 400mm from the top of the appliance, not the frame.
5.5A side wall must be a minimum of 300mm from the side of the appliance, not the frame.
12