Stovax RV40, RV66 Flue Outlet Positions, MInimum dimensions - HEARTH, Site Requirements, Riva

Models: RV66AVC RV55 RV76FK RV40 RV66

1 38
Download 38 pages 55.88 Kb
Page 16
Image 16
1. FLUE OUTLET POSITIONS

SITE REQUIREMENTS

1. FLUE OUTLET POSITIONS

Terminal

Flue

Vertical

Measurement

Horizontal

Measurement

150mm

max

Adjacent

Building

Insulation

 

 

The vertical measurement is the lowest from either the

 

 

point of discharge or 150mm above insulation.

 

 

 

IMPORTANT: Seek

 

Position On Roof

Minimum Clearances

 

specialist advice if installing

 

 

 

A

On ridge or within 600mm

600mm above ridge

in a dwelling with a

thatched roof

B

Elsewhere on roof

2300mm horizontally from roof surface and:

 

 

 

a) 1000mm above highest point of flue exit from roof or

 

 

 

b) as high as the ridge

 

 

 

 

 

C

On pitched, within 2300mm horizontally to

1000mm above top of opening

 

 

openable window, dormer

 

 

D

Within 2300mm of another building

600mm above top of building

 

2. MInimum dimensions - HEARTH

1

Superimposed hearth

or

area to be free of

combustible material

Constructional hearth

 

Riva 40

Riva 55

Riva 66

Riva 66 Avanti

Riva 76

 

RV40

RV55

RV66

RV66 AVC

RV76

 

 

 

 

 

 

A

792mm

932mm

1042mm

1042mm

1162mm

 

 

 

 

 

 

2.1The appliance must stand on a non-combustible constructional hearth which is at least 125mm thick with the minimum dimensions as shown in diagram. If it is to be fitted in a raised setting consideration may need to be given to extending the depth of the hearth to safely containing any falling logs or embers.

2.2The building must have a suitable load-bearing capacity for the hearth and appliance.

Consult a structural engineer for advice before proceeding

2.3When fitting into an existing hearth check:

That the appliance complies with current construction regulations and is at least the minimum sizes shown

2.4If there is no existing fireplace or chimney it is possible to construct a suitable non-combustible housing and hearth setting. The flue must be installed in accordance with all local and national regulations and current rules in force .

Check if adding a new chimney to your property requires planning permission

2.5Some houses are built using a timber frame construction with high levels of thermal insulation. Isolate the appliance from combustible materials, and provide sufficient ventilation to maintain the heating efficiency.

16