SITE REQUIREMENTS
1. FLUE OUTLET POSITIONS
Terminal
Flue
Vertical
Measurement
Horizontal
Measurement
150mm
max
Adjacent
Building
Insulation
|
| The vertical measurement is the lowest from either the | ||
|
| point of discharge or 150mm above insulation. | ||
|
|
| IMPORTANT: Seek | |
| Position On Roof | Minimum Clearances | ||
| specialist advice if installing | |||
|
|
| ||
A | On ridge or within 600mm | 600mm above ridge | in a dwelling with a | |
thatched roof | ||||
B | Elsewhere on roof | 2300mm horizontally from roof surface and: | ||
| ||||
|
| a) 1000mm above highest point of flue exit from roof or |
| |
|
| b) as high as the ridge |
| |
|
|
|
| |
C | On pitched, within 2300mm horizontally to | 1000mm above top of opening |
| |
| openable window, dormer |
|
| |
D | Within 2300mm of another building | 600mm above top of building |
|
2. MInimum dimensions - HEARTH
1
Superimposed hearth
or
area to be free of
combustible material
Constructional hearth
| Riva 40 | Riva 55 | Riva 66 | Riva 66 Avanti | Riva 76 |
| RV40 | RV55 | RV66 | RV66 AVC | RV76 |
|
|
|
|
|
|
A | 792mm | 932mm | 1042mm | 1042mm | 1162mm |
|
|
|
|
|
|
2.1The appliance must stand on a
2.2The building must have a suitable
•Consult a structural engineer for advice before proceeding
2.3When fitting into an existing hearth check:
•That the appliance complies with current construction regulations and is at least the minimum sizes shown
2.4If there is no existing fireplace or chimney it is possible to construct a suitable
•Check if adding a new chimney to your property requires planning permission
2.5Some houses are built using a timber frame construction with high levels of thermal insulation. Isolate the appliance from combustible materials, and provide sufficient ventilation to maintain the heating efficiency.
16