4-2) AC OUTPUT MEASURING

4-2) AC OUTPUT MEASURING

SWITCH LOAD

A

~

TO AC RECEPTACLE

F

V

 

 

~

Use a circuit above for measuring AC output. A hot plate or lamp with a power factor of 1.0 may be used as a load. Adjust the load and rpm, and check that the voltage range is as specified in the following table at the rated amperage and rated rpm.

Rated voltage

60Hz-120V

50Hz-230V

50Hz-240V

 

 

 

 

Voltage range

120-128

230-246

240-256

 

 

 

 

4-3) MEASURING INSULATION RESISTANCE

(1)Connect the megger tester across either one of the two output terminals of the AC receptacle and ground

terminal to measure the insulation resistance. Measure it with the AC breaker on. An insulation resistance of 1 MΩor more is normal.

Original insulation resistance at the time of shipment from the factory is 10 MΩor more.

If it is less than 1 MΩ, disassemble the generator and measure the insulation resistance of the stator, rotor and control panel individually.