83
-
5
15
-
0
00
Rev.
B
8
Cooling and mechanical construction
The Genesys
TM
series is cooled by internal fans. At the installation, care must be taken to allow free
ai
r
flow into the power supply via the front panel and out of the power supply via the rear panel. The
Gen
e
sys
TM
power supplies have a compact and lightweight packag
e, which allows easy installation
and space saving in the application equipment.
1.3 ACCESSORIES
1.3.1
General
Accessories are delivered with the power supply or separately upon ordering. The list belowshows
the possible accessories and ordering n
umbers.
Serial Link Cable
Serial link cable, for linking power supplies by RS485 communication is provided with the power su
p-
ply.
Cable description: 0.5m length, shielded, RJ
-
45 type plugs, 8 contacts (P/N:GEN/RJ
-
45).
Misc. hardware
DB25 plug (AMP, 749809
-
9).
Strain relief for AC cord.
Output terminal shield
Output bus bar connection hardware.
AC cables
AC cables are not provided with the power supply.
Refer to Table 1
-
1
for recommended AC input cables (customer supplied). Add a non
-
locking plug
a
p
proved b
y the national safety standards of the county of usage.
AC Input Range
AC Input Cable
190
-
240V
~
, Three Phase
4 x 1
2
AWG (3 wire plus safety ground), stranded
copper, 300V, 60
°
C minimum, rated for
2
5A. 3m max.
length, outer diameter: 9
~
11mm.
380
-
415V
~
, Th
ree Phase
4 x 1
4
AWG (3 wire plus safety ground), stranded
copper, 600V, 60
°
C minimum, rated for 1
5
A. 3m max.
length, outer diameter: 9
~
11mm.
Table 1
-
1
: Recommended AC input cable
CAUTION
Observe all torque guidelineswithin this manual. Over
-
torquing may da
m
age
Unit or accessories. Such damage is not covered under manufacturers warranty.