PANEL INSTALLATION

1.If applicable, remove optional rear cover of panel (four, 1/4-20 hexhead bolts).

2.Decide if input cables will be fed from bottom-up or top-down.

NOTE

Panels are shipped from the factory for top-down input cable entrance to bay. If you intend to feed input cables from the bottom- up, you must reverse the input terminal plates, as instructed in the following procedure.

If necessary, to change both input buses from top-down to bottom-up input cable entrance, refer to the following illustration and proceed as follows:

a.Remove four, 3/8-in. hex head cap screws securing each input bus assembly to panel.

b.Rotate this assembly for input bus A and resecure it where the bus B had been, and vice versa.

c.Torque bolts to 18 ft-lb (~24 N•m).

Telect, Inc. • USA +1.509.926.6000 • Mexico +1.52.33.3836.3700

 

Poland +1.48.713.239.100 • UK +1.44.1489.889500 • www.telect.com

Page 2-2

Copyright © 2002 Telect, Inc., All Rights Reserved