Alarm Board on

Rear of Panel Cover

Remove 4 Screws

to Remove Panel Cover

Front

Rear

(1X)

(2X)

5.For each contact, insert WAGO tool (supplied) into connector to release contact’s cage-clamp jaws. Insert wire and then pull out tool to cinch.

6.When finished with Feed A and B alarm wiring, resecure alarm panel cover.

— E. Test Inputs & Alarms Without Breakers

1.Make sure BDFB / BDCBB contains no circuit breakers.

2.Turn on Feed A input power.

Verify that VDC PWR lamp turns green.

Verify that FUSE ALM lamp is not lit.

3.Use a DVM with standard .080-in. test probes to verify power and polarity at panel’s VDC test points for Feed A:

Connect panel RED (-48Vdc) to meter RED (voltage).

Connect panel BLK (RTN) to meter BLK (common).

4.Use an ohmmeter at alarm monitor to verify alarm conditions.